No good, Tightening of connecting part, Requirement – Toshiba RAV-SM561AT-E User Manual

Page 23

Advertising
background image

– 23 –

RAV-SM1101AT-E, RAV-SM1401AT-E

Tightening of Connecting Part

(Unit: N•m)

Externally
threaded side

Internally
threaded side

Fix with spanner.

Tighten with torque wrench.

Half union or packed valve

Flare nut

Flare at

indoor unit side

Flare at

outdoor unit side

• Align the centers of the connecting pipes and

tighten the flare nut strong as far as possible with
your fingers.

Then fix the nut with a spanner and tighten it with
torque wrench as shown in the figure.

Cover

Cap

Piping valve

Tightened

Flare nut

Loosened

• As shown in the figure, be sure to use a double

spanner to loosen or tighten the flare nut of the
valve at gas side. If using a single spanner, the nut
cannot be tightened with necessary tightening
torque.

On the contrary, use a single spanner to loosen or
tighten the flare nut of the valve at liquid side.

Cover

NO GOOD

Valve at gas side

• Pressure of R410A is higher than that of R22

(Approx. 1.6 times). Therefore, using a torque
wrench, tighten the flare pipe connecting sections
which connect the indoor/outdoor units at the
specified tightening torque. Incomplete connections
may cause not only a gas leak, but also a trouble of
the refrigeration cycle.

Do not apply refrigerating machine oil to
the flared surface.

REQUIREMENT

1. Do not put the spanner on the cap.

The valve may be broken.

2. If applying excessive torque, the nut may be

broken according to some installation condi-
tions.

• After the installation work, be sure to check gas leak

of connecting part of the pipes with nitrogen.

Outer dia. of copper pipe

6.4 mm (diam.)

9.5 mm (diam.)

12.7 mm (diam.)

15.9 mm (diam.)

Tightening torque

14 to 18 (1.4 to 1.8 kgf•m)

33 to 42 (3.3 to 4.2 kgf•m)

50 to 62 (5.0 to 6.2 kgf•m)

68 to 82 (6.8 to 8.2 kgf•m)