Installation of hanging bolts, Draw-out direction of pipe/cable, Knockout hole of power cable take-in port – Toshiba RAV-SM561AT-E User Manual

Page 123: Pipe knockout hole

Advertising
background image

– 123 –

RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E

Installation of hanging bolts

Use M10 hanging bolts (4 pcs, to be local procure).
Matching to the existing structure, set pitch according
to size in the unit external view as shown below.

Draw-out direction of pipe/cable

• Decide installation place of the unit and draw-out

direction of pipe and cable.

Knockout hole of power cable take-in port

Open the power cable take-in port (Knockout hole)
shown in the external view and then mount the
attached bushing.

New concrete slab

Install the bolts with insert brackets or anchor bolts.

Steel flame structure

Use existing angles or install new support angles.

Existing concrete slab

Use a hole-in anchors, hole-in plugs, or a hole-in bolts.

Pipe knockout hole

• In case of taking pipe from the rear side

* Cut off the groove section with a plastic cutter, etc.

• In case of taking pipe from right side

* Cut off the groove section with a metal saw or

plastic cutter, etc.

• In case of taking pipe from left side

Taking pipe from left side is applied only to the
drain pipe.

The refrigerant pipe cannot be taken out from
the left side.

* Cut off the groove section with a metal saw or

plastic cutter, etc.

• In case of taking pipe from upper side

Taking pipe from upper side is applied only to
the refrigerant pipe.

When taking out the drain pipe from the upper
side, use a drain up kit sold separately.

Open the upper pipe draw-out port (Knockout hole)
shown in the external view.
(Knockout hole of thin plate)

After piping, cut off the attached thermal insulator of
the top plate to pipe shape, and then seal the
knockout hole.

Anchor bolt

(Blade type

bracket)

(Slide type

bracket)

(Pipe hanging

anchor bolt)

Rubber

Hanging bolt

Hanging bolt

Support angle

Rear cover

Grooves

Opened when refrigerant pipe
is taken out from the rear side

Opened when only drain pipe
is taken out from the rear side

100

Groove

Side panel (Right)

Groove

Side panel (Left side))

Advertising