Service port
(Valve core (Setting pin))

Compound pressure gauge

Packed valve at gas side

Pressure gauge

Manifold valve

Handle Hi
(Keep fully closed)

Charge hose
(For R410A only)

Vacuum pump adapter
for counter-flow prevention
(For R410A only)

Handle Lo

Charge hose
(For R410A only)

–101kPa

(–76cmHg)

Vacuum

pump

Valve unit

Valve unit

Charge port

Charge port

Handle
Pull out the handle and
using cutting pliers, etc.
turn it counterclockwise
by 90˚. (Open fully)

Flare nut

Flare nut

Push in handle.

Closed completely

Handle

Opened fully

How to open the valve

Handle position

*1. Use the vacuum pump, vacuum pump adapters,

and gauge manifold referring to the manuals
attached to each tool before using them.
For the vacuum pump, check oil is filled up to the
specified line of the oil gauge.

*2. While the air is purged, check again that the

connecting port of charge hose, which has a
projection to push the valve core, is firmly con-
nected to the charge port.

Valve handling precautions

• Open the valve stem or the handle until it strikes

the stopper. It is unnecessary to apply further
force.

• Securely tighten the cap with a torque wrench.

• Cap tightening torque

Valve size

Ш9.5

Ш15.9

Charge port

33 to 42 N•m (3.3 to 4.2 kgf•m)

20 to 25 N•m (2.0 to 2.5 kgf•m)

14 to 18 N•m (1.4 to 1.8 kgf•m)