RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E

6

REFRIGERANT PIPING AND EVACUATING

Refrigerant piping

1. If the outdoor units are to be mounted on a wall,

make sure that the supporting platform is
sufficiently strong. The platform should be
designed and manufactured to maintain its strength
over a long period of time, and sufficient
consideration should be given to ensuring that the
outdoor unit will not fall.

2. Use copper pipe with 0.8 mm or more

thickness.
(In case pipe size is Ø15.9, with 1.0mm or more.)

3. Flare nut and flare works are also different from

those of the conventional refrigerant.
Take out the flare nut attached to the main unit of
the air conditioner, and use it.

CAUTION

IMPORTANT 4 POINTS FOR PIPING WORK

1. Remove dust and moisture from the inside of

the connecting pipes.

2. Tight connection (between pipes and unit)

3. Evacuate the air in the connecting pipes using

VACUUM PUMP.

4. Check the gas leakage. (connected points)

Permissible piping length and heat

They vary according to the outdoor unit. For details,
refer to the Installation Manual attached to the outdoor
unit.

Flaring

+0
- 0.4

B

• Projection margin in flaring : B (Unit : mm)

Rigid (Clutch type)

• Flaring dia meter size : A (Unit : mm)

*

In the case of flaring for R410A with the conventional
flare tool, pull out it approx.
0.5 mm more than that for R22 to
adjust to the specified flare size.
The copper pipe gauge is useful
for adjusting projection margin size.

Tightening connection

CAUTION

• Do not apply excessive torque. Otherwise, the

nut may crack depending on the conditions.

(Unit : N•m)

• Tightening torque of flare pipe connections

Pressure of R410A becomes higher than that of R22.
(Approx. 1.6 times) Therefore, using a torque
wrench, tighten firmly the flare pipe connecting
sections which connect the
indoor and outdoor units up to
the specified tightening torque.

Incorrect connections may
cause not only a gas leakage,
but also a trouble of the
refrigeration cycle or
compressor damage.

Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.

Flare at

indoor

unit side

Flare at

outdoor

unit side

Half union

Flare nut

Externally
threaded side

Internally
threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

Outer diam. of

copper pipe

6.4 to 15.9

R410A tool used

R410A

R22

0 to 0.5 (Same as left)

Conventional tool used

R410A

R22

1.0 to 1.5

0.5 to 1.0

Outer diam. of copper pipe

6.4

9.5

12.7

15.9

A

R410A

R22

9.1

9.0

13.2

13.0

16.6

16.2

19.7

19.4

Outer diam. of copper pipe

6.4 mm (diam.)

9.5 mm (diam.)

12.7 mm (diam.)

15.9 mm (diam.)

Tightening torque

14 to 18 (1.4 to 1.8 kgf•m)

33 to 42 (3.3 to 4.2 kgf•m)

50 to 62 (5.0 to 6.2 kgf•m)

63 to 77 (6.3 to 7.7 kgf•m)

Insert a flare nut into the pipe, and flare the pipe.

As the flaring sizes of R410A differ from those of
refrigerant R22, the flare tools newly manufactured for
R410A are recommended.

However, the conventional
tools can be used by
adjusting projection margin
of the copper pipe.

Imperial (Wing nut type)

Outer diam. of copper pipe

6.4 or 9.5

12.7 or 15.9

R410A

R22

1.5 to 2.0

1.0 to 1.5

2.0 to 2.5

1.5 to 2.0

A