– 14 –

Concealed Duct High Static Pressure

Installation Manual

EN

„ Duct design

1. In order to prevent short circuits, design the duct installation, so that the intake and discharge openings are not

adjacent to each other.

2. The indoor unit does not have a built-in air filter. Make sure to set up the filter chamber etc. and install the air filter (Locally

procured). If no air filter is installed, the heat exchanger will be blocked by dust, which may cause the malfunction of air
conditioner or the water leakage.

NOTE

All duct connection between units except outdoor unit must be procured and enforced locally.

Duct hose (with heat insulation)

Flexible duct hanging band

Air outlet chamber
(with heat insulation)

Air outlet port
connecting flange

Indoor unit

High efficiency filter
inserting port

Pre filter
inserting port

Air inlet port
connecting flange

Air inlet
chamber

Filter
chamber

Electrical control
box

from ground floor

Duct hose

Check port or carrying
in port (600x600)

Check port cap

Ceiling

Air outlet port

Air outlet port

to ground floor

<Duct installation example (First floor)>

14-EN

Advertising