Concealed Duct High Static Pressure

Installation Manual

Procedure

6

When settings have been completed, push

button to

determine the settings.
When

button is pushed, “SETTING” flashes and then the

display content disappears and the air conditioner enters the
normal stop mode.
(While “SETTING” is flashing, no operation of the remote
controller is accepted.)

„ Filter sign setting

According to the installation condition, the filter sign term
(Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
(

1

o

2

o

3

o

4

o

5

o

6

).

• For the CODE No. in Procedure

3

, specify [01].

• For the [SET DATA] in Procedure

4

, select the SET DATA

of filter sign term from the following table.

„ To secure better effect of

heating

When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the room,
the detection temperature of heating can be raised. Also use
a circulator, etc. to circulate heat air near the ceiling.
Follow to the basic operation procedure
(

1

o

2

o

3

o

4

o

5

o

6

).

• For the CODE No. in Procedure

3

, specify [06].

• For the set data in Procedure

4

, select the SET DATA of

shift value of detection temperature to be set up from the
table below.

„ Power saving mode

1. Push

button for at least four seconds when

the air conditioner is not working.

flashes.

Indicates CODE No. “C2.”

2. Select an indoor unit to be set by pushing

(left

side of the button).
Each time you push the button, unit numbers change as
follows:

The fan of the selected unit runs.

3. Adjust the power save setting by pushing TIME

buttons.
Each push of the button changes the power level by 1%
within the range from 100% to 50%.

* The factory default is 75%.

4. Determine the setting by pushing

button.

5. Push

button to complete the setting.

SET DATA

Filter sign term

0000

None

0001

150H

0002

2500H

(Factory default)

0003

5000H

0004

10000H

SET DATA

Detection temperature shift value

0000

No shift

0001

+1°C

0002

+2°C

(Factory default)

0003

+3°C

0004

+4°C

0005

+5°C

0006

+6°C

UNIT No.
1-1

UNIT No.
1-2

UNIT No.
1-3

UNIT No.
1-4

Setting of power level in
power saving mode

29-EN