Toshiba RAV-SM2242DT-E User Manual

Page 34

Advertising
background image

– 33 –

Concealed Duct High Static Pressure

Installation Manual

Procedure

6

If there is other indoor unit to be changed, repeat procedure

2

to

5

to change the setup.

When the above setup has finished, push

to select

the indoor UNIT No. before change of setup, specify CODE
No. [12], [13], [14] in order with TEMP.

/

buttons,

and then check the changed contents.

Address change check Before change:
[3-3-1] o After change: [2-2-2]

Pushing

button clears the contents of which setup was

changed.
(In this case, procedure from

2

is repeated.)

Procedure

7

After check of the changed contents, push

button. (Setup

is determined.) When pushing

button, the display

disappears and the status becomes the usual stop status.
(When pushing

button the operation from the remote

controller is not accepted for approx. 1 minute.)
* If the operation from the remote controller is not accepted

even 1 minute or more passed after pushing

button, it

is considered that the address setup is incorrect.
In this case, the automatic address must be again set up.
Therefore repeat procedure of the setup change from
the Procedure

1

.

To recognize the position of the
corresponding indoor unit though the
indoor UNIT No. is known

Check the position during operation stop.
(Be sure to stop operation of the set.)

Procedure

1

Push simultaneously

+

buttons for 4 seconds or

more.
After a while, the display part flashes and the display appears
as shown below.
In this time, the position can be checked because fan of the
indoor unit operate.
• For the group control, the indoor UNIT No. is displayed as

[

] and fans of all the indoor units in the group control

operate.
Check the displayed CODE No. is [01].

• When the CODE No. is other than [01], push

button to

erase the display and repeat procedure from the first step.
(After pushing

button, operation of the remote controller

is not accepted for approx. 1 minute.)

Procedure

2

In the group control, every pushing

button, the

indoor UNIT No. in the group control is displayed in order.
In this time, the position of the indoor unit can be confirmed
because only fan of the selected indoor unit operate.
(For a group control, No. of the firstly displayed indoor unit
becomes the header unit.)

Procedure

3

After confirmation, push

button to return the mode to the

usual mode.
When pushing

button, the display disappears and the

status becomes the usual stop status.
(When pushing

button the operation from the remote

controller is not accepted for approx. 1 minute.)

Indoor UNIT No. before setup change is displayed.

2

1,3

1

(* Display changes according to
the model No. of indoor unit.)

33-EN