Toshiba RAV-SM2242DT-E User Manual

Page 33

Advertising
background image

– 32 –

Concealed Duct High Static Pressure

Installation Manual

EN

Procedure example 1

Manual address setup procedure
While the operation stops, change the setup.
(Be sure to stop the operation of the unit.)

Procedure

1

Push simultaneously

+

+

buttons for 4 seconds or

more. After a while, the display part flashes as shown below.
Check the displayed CODE No. is [10].
• When the CODE No. is other than [10], push

button to

erase the display and repeat procedure from the first step.
(After pushing

button, operation of the remote

controller is not accepted for approx. 1 minute.)
(For a group control, No. of the firstly displayed indoor unit
becomes the header unit.)

Procedure

2

Every pushing

button, the indoor UNIT No. in the

group control is displayed in order. Select the indoor unit of
which setup is changed.
In this time, the position of the indoor unit of which setup is
changed can be confirmed because fan of the selected
indoor unit operate.

Procedure

3

1. Using TEMP.

/

buttons, specify CODE No.

[12].
(CODE No. [12]: Line address)

2. Using TIME

/

buttons, change the line address

from [

3] to [2].

3. Push

button.

In this time, the setup finishes when the display changes
from flashing to lighting.

Procedure

4

1. Using TEMP.

/

buttons, specify CODE No.

[13].
(CODE No. [13]: Indoor address)

2. Using TIME

/

buttons, change the indoor

address from [3] to [2].

3. Push

button.

In this time, the setup finishes when the display changes
from flashing to lighting.

Procedure

5

1. Using TEMP.

/

buttons, specify CODE No.

[14].
(CODE No. [14]: Group address)

2. Using TIME

/

buttons, change the SET DATA

from [

0001] to [0002].

(SET DATA [Header unit: 0001] [Follower unit: 0002])

3. Push

button.

In this time, the setup finishes when the display changes
from flashing to lighting.

2,6

1

7

3

-1,

4

5

6

-1,
-1,

7

3

-3,

4

-3,

3

-2,

4

-2,

5

-2

5

-3,

(* Display changes according to
the model No. of indoor unit.)

Indoor unit No. before setup change is displayed.

Indoor unit No. before setup change is displayed.

Indoor UNIT No. before setup change is displayed.

32-EN