Toshiba RAV-SM2242DT-E User Manual

Page 41

Advertising
background image

– 40 –

Concealed Duct High Static Pressure

Installation Manual

EN

: The air conditioner automatically enters the auto-address setting mode.

L20

LAN communication error

Network
adapter central
control

Address setting, central control remote controller, network adapter ---
Duplication of address in central control communication

Auto-reset

L29

Other outdoor unit error

Outdoor

Other outdoor unit error

Entire stop

1) Communication error between IPDU MCU and CDB MCU

Entire stop

2) Abnormal temperature was detected by the heat sink temp. sensor
in IGBT.

L30

Abnormal external input into
indoor unit (interlock)

Indoor

External devices, outdoor unit P.C. board --- Abnormal stop due to
incorrect external input into CN80

Entire stop

L31

Phase sequence error, etc.

Outdoor

Power supply phase sequence, outdoor unit P.C. board --- Abnormal
phase sequence of the 3-phase power supply

Operation
continued
(thermostat
OFF)

P01

Indoor unit fan error

Indoor

Indoor fan motor, indoor P.C. board --- Indoor AC fan error (fan motor
thermal relay activated) was detected.

Entire stop

P03

Outdoor unit discharge temp.
error

Outdoor

An error was detected in the discharge temp. releasing control.

Entire stop

P04

Outdoor unit high-pressure
system error

Outdoor

High-pressure switch --- The IOL was activated or an error was
detected in the high-pressure releasing control using the TE.

Entire stop

P05

Open phase detected

Outdoor

The power supply wire may be connected incorrectly. Check open
phase and voltages of the power supply.

Entire stop

P07

Heat sink overheat

Outdoor

Abnormal temperature was detected by the temp. sensor of the IGBT
heat sink.

Entire stop

P10

Indoor unit water overflow
detected

Indoor

Drain pipe, clogging of drainage, float switch circuit, indoor P.C. board
--- Drainage is out of order or the float switch was activated.

Entire stop

P15

Gas leakage detected

Outdoor

There may be gas leakage from the pipe or connecting part. Check for
gas leakage.

Entire stop

P19

4-way valve error

Outdoor
(Indoor)

4-way valve, indoor temp. sensors (TC/TCJ) --- An error was detected
due to temperature drop of the indoor unit heat exchanger sensor
when heating.

Auto-reset
(Auto-reset)

P20

High-pressure protective
operation

Outdoor

High-pressure protection

Entire stop

P22

Outdoor unit fan error

Outdoor

Outdoor unit fan motor, outdoor unit P.C. board --- An error
(overcurrent, locking, etc.) was detected in the outdoor unit fan drive
circuit.

Entire stop

P26

Outdoor unit inverter Idc
activated

Outdoor

IGBT, outdoor unit P.C. board, inverter wiring, compressor --- Short-
circuit protection for compressor drive circuit devices (G-Tr/IGBT) was
activated.

Entire stop

P29

Outdoor unit position error

Outdoor

Outdoor unit P.C. board, high-pressure switch --- Compressor motor
position error was detected.

Entire stop

P31

Other indoor unit error

Indoor

Another indoor unit in the group is raising an alarm.

Entire stop

E03/L07/L03/L08 alarm check locations and error description

Auto-reset

Wired remote

controller

display

Main defective parts

Judging device

Parts to be checked / error description

Air conditioner

status

Indication

40-EN