Remote controller switch monitoring function – Toshiba RAV-SM2242DT-E User Manual

Page 31

Advertising
background image

– 30 –

Concealed Duct High Static Pressure

Installation Manual

EN

„ Remote controller switch

monitoring function

This function is available to call the service monitor mode
from the remote controller during a test run to acquire
temperatures of sensors of the remote controller, indoor unit,
and outdoor unit.

1. Push

and

buttons simultaneously for at least

4 seconds to call the service monitor mode.
The service monitor indicator lights up and the
header indoor unit number is displayed first. CODE
No.

is also displayed.

2. Pushing TEMP.

buttons, select the number of

sensor, etc. (CODE No.) to be monitored. (See the
following table.)

3. Pushing

(left side of the button), select an indoor

unit to be monitored. The sensor temperatures of indoor
units and their outdoor unit in the control group are
displayed.

4. Push

button to return to the normal display.

Indoor unit data

CODE No.

Data name

01

Room temperature (remote controller)

02

Indoor unit intake air temperature (TA)

03

Indoor unit heat exchanger (coil)

temperature (TCJ)

04

Indoor unit heat exchanger (coil)

temperature (TC)

F3

Indoor unit fan cumulative operating hours

(x1 h)

1

3

4

2

Outdoor unit data

CODE No.

Data name

60

Outdoor unit heat exchanger (coil)

temperature (TE)

61

Outside air temperature (TO)

62

Compressor discharge temperature (TD)

63

Compressor suction temperature (TS)

64

65

Heatsink temperature (THS)

6A

Operating current (x1/10)

F1

Compressor cumulative operating hours

(x100h)

30-EN

Advertising