Error codes and parts to be checked – Toshiba RAV-SM2242DT-E User Manual

Page 40

Advertising
background image

– 39 –

Concealed Duct High Static Pressure

Installation Manual

„ Error codes and parts to be checked

Wired remote

controller

display

Main defective parts

Judging device

Parts to be checked / error description

Air conditioner

status

Indication

E01

No header remote controller

Remote
controller

Incorrect remote controller setting --- The header remote controller has
not been set (including two remote controllers).

*

Remote controller
communication error

No signal can be received from the indoor unit.

E02

Remote controller transmission
error

Remote
controller

System interconnecting wires, indoor P.C. board, remote controller
--- No signal can be sent to the indoor unit.

*

E03

Indoor unit-remote controller
regular communication error

Indoor

Remote controller, network adapter, indoor P.C. board --- No data is
received from the remote controller or network adapter.

Auto-reset

E04

Indoor unit-outdoor unit serial
communication error

Indoor

System interconnecting wires, indoor P.C. board, outdoor P.C. board -
-- Serial communication error between indoor unit and outdoor unit

Auto-reset

IPDU-CDB communication error

E08

Duplicated indoor addresses

Indoor

Indoor address setting error --- The same address as the self-address
was detected.

Auto-reset

E09

Duplicated header remote
controllers

Remote
controller

Remote controller address setting error --- Two remote controllers are
set as header in the double-remote controller control.

*

(* The header indoor unit stops raising alarm and follower indoor units
continue to operate.)

E10

CPU-CPU communication error

Indoor

Indoor P.C. board --- Communication error between main MCU and
motor microcomputer MCU

Auto-reset

E18

Header indoor unit-indoor
follower unit regular
communication error

Indoor

Indoor P.C. board --- Regular communication is not possible between
header and follower indoor units or between twin header (main) and
follower (sub) units.

Auto-reset

E31

IPDU communication error

Outdoor

Communication error between IPDU and CDB

Entire stop

F01

Indoor unit heat exchanger
sensor (TCJ) error

Indoor

Heat exchanger sensor (TCJ), indoor P.C. board --- Open-circuit or
short-circuit of the heat exchanger sensor (TCJ) was detected.

Auto-reset

F02

Indoor unit heat exchanger
sensor (TC) error

Indoor

Heat exchanger sensor (TC), indoor P.C. board --- Open-circuit or
short-circuit of the heat exchanger sensor (TC) was detected.

Auto-reset

F04

Outdoor unit discharge temp.
sensor (TD) error

Outdoor

Outdoor temp. sensor (TD), outdoor P.C. board --- Open-circuit or
short-circuit of the discharge temp. sensor was detected.

Entire stop

F06

Outdoor unit temp. sensor (TE/
TS) error

Outdoor

Outdoor temp. sensors (TE/TS), outdoor P.C. board --- Open-circuit or
short-circuit of the heat exchanger temp. sensor was detected.

Entire stop

F07

TL sensor error

Outdoor

TL sensor may be displaced, disconnected or short-circuited.

Entire stop

F08

Outdoor unit outside air temp.
sensor error

Outdoor

Outdoor temp. sensor (TO), outdoor P.C. board --- Open-circuit or
short-circuit of the outdoor air temp. sensor was detected.

Operation
continued

F10

Indoor unit room temp. sensor
(TA) error

Indoor

Room temp. sensor (TA), indoor P.C. board --- Open-circuit or short-
circuit of the room temp. sensor (TA) was detected.

Auto-reset

F12

TS (1) sensor error

Outdoor

TS (1) sensor may be displaced, disconnected or short-circuited.

Entire stop

F13

Heat sink sensor error

Outdoor

Abnormal temperature was detected by the temp. sensor of the IGBT
heat sink.

Entire stop

F15

Temp. sensor connection error

Outdoor

Temp. sensor (TE/TS) may be connected incorrectly.

Entire stop

F29

Indoor unit, other P.C. board
error

Indoor

Indoor P.C. board --- EEPROM error

Auto-reset

F31

Outdoor unit P.C. board

Outdoor

Outdoor P.C. board ---- In the case of EEPROM error.

Entire stop

H01

Outdoor unit compressor
breakdown

Outdoor

Current detect circuit, power voltage --- Minimum frequency was
reached in the current releasing control or short-circuit current (Idc)
after direct excitation was detected

Entire stop

H02

Outdoor unit compressor lock

Outdoor

Compressor circuit --- Compressor lock was detected.

Entire stop

H03

Outdoor unit current detect circuit
error

Outdoor

Current detect circuit, outdoor unit P.C. board --- Abnormal current was
detected in AC-CT or a phase loss was detected.

Entire stop

H04

Case thermostat operation (1)

Outdoor

Malfunction of the case thermostat

Entire stop

H06

Outdoor unit low-pressure
system error

Outdoor

Current, high-pressure switch circuit, outdoor P.C. board --- Ps
pressure sensor error was detected or low-pressure protective
operation was activated.

Entire stop

L03

Duplicated header indoor units

Indoor

Indoor address setting error --- There are two or more header units in
the group.

Entire stop

L07

Group line in individual indoor
unit

Indoor

Indoor address setting error --- There is at least one group-connected
indoor unit among individual indoor units.

Entire stop

L08

Indoor group address not set

Indoor

Indoor address setting error --- Indoor address group has not been set. Entire stop

L09

Indoor power level not set

Indoor

Indoor power level has not been set.

Entire stop

L10

Outdoor unit P.C. board

Outdoor

In the case of outdoor P.C. board jumper wire (for service) setting error Entire stop

39-EN