6.17.12 Undervoltage trip

H

: Undervoltage trip/alarm selection

• Function

This parameter is used for selecting the control mode when an undervoltage is detected. Trip
information is displayed as "WR".

H

=: The inverter is stopped. However, it is not tripped (Failure signal FL not activated).

The inverter is stopped when the voltage does not exceed 60 % or less of its rating.

H

=: Inverter is stopped. It is also tripped (Failure signal FL activated), only after detection of a voltage

not exceeding 60% or less of its rating.

H

=: Inverter is stopped. However, it is not tripped (Failure signal FL not activated). The inverter stop

(Failure signal FL not activated.), only after detection of a voltage not exceeding 50% of its rating.
Be sure to connect the input reactor.

Title

Function

Adjustment range

Default setting

H

Undervoltage trip/alarm
selection

0: Alarm only (detection level below 60%)
1: Tripping (detection level below 60%)
2: Alarm only (detection level below 50%,

input reactor needed)

0