Table of output terminal functions 3 – Toshiba VF-FS1 User Manual
Page 227
E6581381
K-19
11
■
Table of output terminal functions 3
Function
No.
Code
Function
Action
53
PIDFN
Inversion of signal in accordance of frequency
command (VIA)
Inversion of PIDF setting
54
MOFF
Undervoltage detection
ON: Undervoltage detected
OFF: Other than undervoltage
55
MOFFN
Inversion of undervoltage detection
Inversion of MOFF
56
LOC
Local/remote switching
ON: Local mode
OFF: Remote mode
57
LOCN
Inversion of local/remote switching
Inversion of LOC
58
PTC
PTC thermal alarm
ON: 60% and over the protection level by PTC
OFF: Normal condition
59
PTCN
Inversion of PTC thermal alarm
Inversion of PTC
60
PIDFB
Signal in accordance of frequency command (VIB)
ON: Frequency commanded by HOQF or
H
and that by VIB show the same
value.
OFF: Frequency commanded by HOQF or
H
and that by VIB show different
values.
61
PIDFBN
Inversion of signal in accordance of frequency
command (VIB)
Inversion of PIDFB setting
62-253
Disabled
Invalid settings, always OFF (ignored)
Invalid settings, always OFF (ignored)
254
AOFF
Always OFF
Always OFF
255
AON
Always ON
Always ON