Table of output terminal functions 3 – Toshiba VF-FS1 User Manual

Page 227

Advertising
background image

E6581381

K-19

11

Table of output terminal functions 3

Function

No.

Code

Function

Action

53

PIDFN

Inversion of signal in accordance of frequency
command (VIA)

Inversion of PIDF setting

54

MOFF

Undervoltage detection

ON: Undervoltage detected
OFF: Other than undervoltage

55

MOFFN

Inversion of undervoltage detection

Inversion of MOFF

56

LOC

Local/remote switching

ON: Local mode
OFF: Remote mode

57

LOCN

Inversion of local/remote switching

Inversion of LOC

58

PTC

PTC thermal alarm

ON: 60% and over the protection level by PTC
OFF: Normal condition

59

PTCN

Inversion of PTC thermal alarm

Inversion of PTC

60

PIDFB

Signal in accordance of frequency command (VIB)

ON: Frequency commanded by HOQF or

H

and that by VIB show the same

value.

OFF: Frequency commanded by HOQF or

H

and that by VIB show different

values.

61

PIDFBN

Inversion of signal in accordance of frequency
command (VIB)

Inversion of PIDFB setting

62-253

Disabled

Invalid settings, always OFF (ignored)

Invalid settings, always OFF (ignored)

254

AOFF

Always OFF

Always OFF

255

AON

Always ON

Always ON