E6581381

E-11

5

Resolution

All FM terminals have a maximum of 1/1000.

Example of 4-20mA output adjustment

⇒ For details, see section 6.19.1.

H

=1, H=0

H

=1, H=20

H

Output

currrent

Output

currrent

Internal calculated value

Internal calculated value

Note 1: When using the FM terminal for current output, be sure that the external load resistance is less than 750

Ω.

Note 2: Note that, if HOUN is set to  (torque), data will be updated at intervals of more than 40 ms.

Adjustment scale with parameter HO (Meter adjustment)

Connect meters as shown below.

FM

CC

Meter: Frequency meter
(default setting)

VF-FS1

FM

CC

VF-FS1

The reading of the
frequency meter
will fluctuate during
scale adjustment.

Meter: ammeter
(HOUN=)

The reading of the
ammeter will
fluctuate during
scale adjustment.

+

-

+

-

* Optional frequency meter: QS-60T

* Make the maximum ammeter scale at least 120 percent

of the inverter's rated output current.

<Frequency meter>

<Ammeter>