Toshiba VF-FS1 User Manual

Page 215

Advertising
background image

E6581381

K-7

11

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

0: Supply voltage uncorrected, output

voltage limited

1: Supply voltage corrected, output

voltage limited

2: Supply voltage uncorrected, output

voltage unlimited

H

0307

Supply voltage
correction
(limitation of
output voltage)

-

-

3: Supply voltage corrected, output

voltage unlimited

2

6.12.5

H

0311

Reverse-run
prohibition

-

-

0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited

0

6.12.6

H

0312

Random mode

-

-

0: Disabled
1: Automatic setting

0

6.11

0: Carrier frequency not reduced

automatically

1: Carrier frequency reduced

automatically

2: Carrier frequency not reduced

automatically
Support for 400V models

H

0316

Carrier frequency
control mode
selection

-

-

3: Carrier frequency reduced

automatically
Support for 400V models

1

H

0320

Droop gain

1/1

0-100

0

6.13

H

0323

Droop insensitive
torque band

1/1

0-100

10

H

0359

PID control
waiting time

s

1/1

0-2400

0

6.14

H

0360

PID control

-

-

0: Disabled,
1: Enabled (Feedback: VIA)
2: Enabled (Feedback: VIB)

0

H

0362

Proportional gain

-

0.01/0.01

0.01-100.0

0.30

H

0363

Integral gain

-

0.01/0.01

0.01-100.0

0.20

H

0366

Differential gain

-

0.01/0.01

0.00-2.55

0.00

*1 : Default values vary depending on the capacity.

⇒ See the table of page K-14.