Toshiba VF-FS1 User Manual

Page 32

Advertising
background image

E6581381

A-20

1

•

Do not install in any location of high temperature, high humidity,
moisture condensation and freezing and avoid locations where
there is exposure to water and/or where there may be large
amounts of dust, metallic fragments and oil mist.

•

Do not install in any location where corrosive gases or grinding
fluids are present.

•

Operate in areas where ambient temperature ranges from -10°C to 60°C.
When installing the inverter where the ambient temperature will rise above 40°C, remove the label
(seal) from the top and operate it at a current lower than the rated one.

5cm

5cm

Measurement position

Measurement position

5cm

Note:

The inverter is a heat-emitting body. Make sure proper space and ventilation is provided when
installing in the cabinet. When installing inside a cabinet, we recommend the top seal peeled off
although 40°C or less.

•

Do not install in any location that is subject to large amounts of vibration.

Note:

If the VF-FS1 Inverter is installed in a location that is subject
to vibration, anti-vibration measures are required. Please
consult with Toshiba about these measures.

•

If the VF-FS1 Inverter is installed near any of the equipment listed below, provide measures to insure
against errors in operation.

Solenoids:

Attach surge suppressor on coil.

Brakes:

Attach surge suppressor on coil.

Magnetic contactors: Attach surge suppressor on coil.
Fluorescent lights:

Attach surge suppressor on coil.

Resistors:

Place far away from VF-FS1 Inverter.

Resistors