Western Telematic MPC-20VS16-3 User Manual

Page 119

Advertising
background image

7-8

Alarm Configuration

Plug Access: Determines which Plug(s) will be switched when the current load

exceeds the Alarm Set Threshold and the Load Shedding feature is triggered at
the selected unit/branch/line. For example, if plugs A1, A2 and A3 are selected,
then these plugs will be switched On or Off whenever the current load exceeds
the Alarm Set Threshold at the selected unit/branch/line. (Default = undefined.)

Notes:

• In the Web Browser Interface, Plug Access is configured by clicking on the

"plus" symbol in the "Configure Plug Access" field to display the drop down
menu, and then selecting the desired Plug(s) from the drop down menu.

• If your installation includes optional AUX units, please refer to Section 7.1.1.3

for additional instructions regarding granting access to plugs on AUX units.

Plug Group Access: Determines which Plug Group(s) will be switched when

the current exceeds the Alarm Set Threshold and the Load Shedding feature is
triggered at the selected unit/branch/line. For example, if you have defined a
Plug Group named "test", which includes Plugs B3, B4 and B5, and then selected
the "test" Plug Group via the Plug Group Access parameter, then all of the plugs
in the "test" Plug Group will be switched On or Off whenever the current exceeds
the Alarm Set Threshold at the selected unit/branch/line. (Default = undefined.)

Notes:

• In the Web Browser Interface, Plug Group Access is configured by clicking

on the "plus" symbol in the "Configure Plug Group Access" field to display
the drop down menu, and then selecting the desired Plug Group(s) from the
drop down menu.

• Plug Groups must first be defined (as described in Section 5.6) before they

will be displayed in the Load Shedding menu's Plug Group Access submenu.

4. After setting parameters for a given unit and branch or line, you may also define

additional parameters for other attached units or branches. To set Load Shedding
parameters for other units, branches or lines, return to the Alarm Configuration
menu and then repeat steps two and three.

Advertising