York YCUL0016 User Manual

Page 105

Advertising
background image

YORK INTERNATIONAL

104

YORK INTERNATIONAL

105

FORM 150.63-EG1

SYSTEM #2 FIELD SUPPLIED WIRING

SYSTEM #2 COMPRESSOR & FAN

MCA

1

MIN N/F

DISC SW

2

D.E. FUSE

CKT. BKR.

5

INCOMING

(LUGS) WIRE

RANGE

6

COMPR. #1

COMPR. #2

COMPR. #3

FANS

MIN

3

MAX

4

MIN

MAX

RLA

LRA

RLA

LRA

RLA

LRA

QTY

FLA (EA)

92

100

100

110

100

110

# 10 - # 1

33.2

278

33.2

278

2

8.2

91

100

100

110

100

110

# 10 - # 1

33.2

278

33.2

278

2

7.8

55

60

60

70

60

70

# 10 - # 1

19.9

151

19.9

151

2

4.8

46

60

50

60

50

60

# 10 - # 1

16.6

127

16.6

127

2

4.0

37

60

40

45

40

45

# 10 - # 1

13.3

100

13.3

100

2

3.1

92

100

100

110

100

110

# 10 - # 1

33.2

278

33.2

278

2

8.2

91

100

100

110

100

110

# 10 - # 1

33.2

278

33.2

278

2

7.8

55

60

60

70

60

70

# 10 - # 1

19.9

151

19.9

151

2

4.8

46

60

50

60

50

60

# 10 - # 1

16.6

127

16.6

127

2

4.0

37

60

40

45

40

45

# 10 - # 1

13.3

100

13.3

100

2

3.1

107

150

125

125

125

125

# 10 - # 1

40.0

350

40.0

350

2

8.2

106

150

125

125

125

125

# 10 - # 1

40.0

350

40.0

350

2

7.8

64

100

70

80

70

80

# 10 - # 1

24.0

195

24.0

195

2

4.8

53

60

60

70

60

70

# 10 - # 1

19.9

167

19.9

167

2

4.0

43

60

50

50

50

50

# 10 - # 1

16.0

125

16.0

125

2

3.1

107

150

125

125

125

125

# 10 - # 1

40.0

350

40.0

350

2

8.2

106

150

125

125

125

125

# 10 - # 1

40.0

350

40.0

350

2

7.8

64

100

70

80

70

80

# 10 - # 1

24.0

195

24.0

195

2

4.8

53

60

60

70

60

70

# 10 - # 1

19.9

167

19.9

167

2

4.0

43

60

50

50

50

50

# 10 - # 1

16.0

125

16.0

125

2

3.1

124

150

150

150

150

150

# 10 - 3/0

47.8

425

47.8

425

2

8.2

124

150

150

150

150

150

# 10 - 3/0

47.8

425

47.8

425

2

7.8

75

100

90

100

90

100

# 10 - # 1

28.7

239

28.7

239

2

4.8

62

100

70

80

70

80

# 10 - # 1

23.9

198

23.9

198

2

4.0

50

60

60

60

60

60

# 10 - # 1

19.1

148

19.1

148

2

3.1

125

150

150

150

150

150

# 10 - 3/0

33.2

278

33.2

278

33.2

278

2

8.2

124

150

150

150

150

150

# 10 - 3/0

33.2

278

33.2

278

33.2

278

2

7.8

75

100

80

90

80

90

# 10 - # 1

19.9

151

19.9

151

19.9

151

2

4.8

62

100

70

70

70

70

# 10 - # 1

16.6

127

16.6

127

16.6

127

2

4.0

50

60

60

60

60

60

# 10 - # 1

13.3

100

13.3

100

13.3

100

2

3.1

147

200

175

175

175

175

# 10 - 3/0

40.0

350

40.0

350

40.0

350

2

8.2

146

200

175

175

175

175

# 10 - 3/0

40.0

350

40.0

350

40.0

350

2

7.8

88

100

100

110

100

110

# 10 - # 1

24.0

195

24.0

195

24.0

195

2

4.8

73

100

80

90

80

90

# 10 - # 1

19.9

167

19.9

167

19.9

167

2

4.0

59

100

70

70

70

70

# 10 - # 1

16.0

125

16.0

125

16.0

125

2

3.1

147

200

175

175

175

175

# 10 - 3/0

40.0

350

40.0

350

40.0

350

2

8.2

146

200

175

175

175

175

# 10 - 3/0

40.0

350

40.0

350

40.0

350

2

7.8

88

100

100

100

100

100

# 10 - # 1

24.0

195

24.0

195

24.0

195

2

4.8

73

100

80

90

80

90

# 10 - # 1

19.9

167

19.9

167

19.9

167

2

4.0

59

100

70

70

70

70

# 10 - # 1

16.0

125

16.0

125

16.0

125

2

3.1

172

200

200

200

200

200

# 10 - 3/0

47.8

425

47.8

425

47.8

425

2

8.2

171

200

200

200

200

200

# 10 - 3/0

47.8

425

47.8

425

47.8

425

2

7.8

103

150

125

125

125

125

# 10 - # 1

28.7

239

28.7

239

28.7

239

2

4.8

86

100

100

100

100

100

# 10 - # 1

23.9

198

23.9

198

23.9

198

2

4.0

69

100

80

80

80

80

# 10 - # 1

19.1

148

19.1

148

19.1

148

2

3.1

YCUL0046 - YCUL0090

DUAL POINT POWER SUPPLY CONNECTIONS (see Fig. 2)

(Two Field Provided Power Supply Circuits to the condensing unit. Field connections to Factory Provided Terminal Blocks per system.)

Advertising