York YCUL0016 User Manual

Page 109

Advertising
background image

YORK INTERNATIONAL

108

YORK INTERNATIONAL

109

FORM 150.63-EG1

SYSTEM #1 COMPRESSOR & FAN

COMPR. #1

COMPR. #2

COMPR. #3

FANS

RLA

LRA

RLA

LRA

RLA

LRA

QTY

FLA(EA)

100.2

550

100.2

550

3

8.2

92.8

550

92.8

550

3

7.8

53.5

305

53.5

305

3

4.8

44.2

270

44.2

270

3

4.0

35.4

210

35.4

210

3

3.1

100.2

550

100.2

550

3

8.2

92.8

550

92.8

550

3

7.8

53.5

305

53.5

305

3

4.8

44.2

270

44.2

270

3

4.0

35.4

210

35.4

210

3

3.1

73.9

450

73.9

450

73.9

450

4

8.2

68.5

450

68.5

450

68.5

450

4

7.8

39.5

260

39.5

260

39.5

260

4

4.8

32.6

215

32.6

215

32.6

215

4

4.0

26.1

180

26.1

180

26.1

180

4

3.1

73.9

450

73.9

450

73.9

450

4

8.2

68.5

450

68.5

450

68.5

450

4

7.8

39.5

260

39.5

260

39.5

260

4

4.8

32.6

215

32.6

215

32.6

215

4

4.0

26.1

180

26.1

180

26.1

180

4

3.1

100.2

550

100.2

550

100.2

550

4

8.2

92.8

550

92.8

550

92.8

550

4

7.8

53.5

305

53.5

305

53.5

305

4

4.8

44.2

270

44.2

270

44.2

270

4

4.0

35.4

210

35.4

210

35.4

210

4

3.1

SYSTEM #2 COMPRESSOR & FAN

COMPR. #1

COMPR. #2

COMPR. #3

FANS

RLA

LRA

RLA

LRA

RLA

LRA

QTY

FLA(EA)

73.9

450

73.9

450

3

8.2

68.5

450

68.5

450

3

7.8

39.5

260

39.5

260

3

4.8

32.6

215

32.6

215

3

4.0

26.1

180

26.1

180

3

3.1

100.2

550

100.2

550

3

8.2

92.8

550

92.8

550

3

7.8

53.5

305

53.5

305

3

4.8

44.2

270

44.2

270

3

4.0

35.4

210

35.4

210

3

3.1

100.2

550

100.2

550

4

8.2

92.8

550

92.8

550

4

7.8

53.5

305

53.5

305

4

4.8

44.2

270

44.2

270

4

4.0

35.4

210

35.4

210

4

3.1

73.9

450

73.9

450

73.9

450

4

8.2

68.5

450

68.5

450

68.5

450

4

7.8

39.5

260

39.5

260

39.5

260

4

4.8

32.6

215

32.6

215

32.6

215

4

4.0

26.1

180

26.1

180

26.1

180

4

3.1

73.9

450

73.9

450

73.9

450

4

8.2

68.5

450

68.5

450

68.5

450

4

7.8

39.5

260

39.5

260

39.5

260

4

4.8

32.6

215

32.6

215

32.6

215

4

4.0

26.1

180

26.1

180

26.1

180

4

3.1

YCUL0096 - YCUL0130

MULTIPLE POINT POWER SUPPLY CONNECTIONS (see Fig. 3)

(Two Field Provided Power Supply Circuits to the condensing unit. Field connections to Factory Provided Terminal Blocks (standard), Non-Fused Disconnect

Switches (optional) or Individual System Circuit Breakers (optional) per electrical system.)

Advertising
This manual is related to the following products: