Dimensions – York YCUL0016 User Manual

Page 78

Advertising
background image

YORK INTERNATIONAL

78

YORK INTERNATIONAL

79

FORM 150.63-EG1

NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable

operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable

airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure

safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center

assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m; rear to wall –

2m; control panel to end wall – 1.2m; top – no obstructions allowed; distance between adjacent units – 3m. No more than one

adjacent wall may be higher than the unit.

Dimensions -

YCUL0016 - YCUL0026 (SI)

������������������������

�������������

���������������������

���������������������

�����������

�������

�������

����

���

��

���

���

��

���

��

���

�����������

����������

������

�����

���

������������

MODEL YCUL

A

0016

567

0026

564