FORM 150.63-EG1

low suction pressure, high pressure switch, and

motor protector. Compressor motor protector

shall protect against damage due to high input

current or thermal overload of windings.

9. Unit Safeties: Shall be automatic reset and

cause compressors to shut down if low ambient,

or under voltage.

10. Alarm Contacts: Low ambient, low voltage,

low battery, and (per compressor circuit):

high discharge pressure, and low suction

pressure.

D. Manufacturer shall provide any controls not listed

above, necessary for automatic condensing unit

operation. Mechanical Contractor shall provide

field control wiring necessary to interface sensors

to the condensing unit control system.

2.06 POWER CONNECTION AND

DISTRIBUTION

A. Power Panels:

1. NEMA 3R/12 (IP55) rain/dust tight, powder

painted steel cabinets with hinged, latched, and

gasket sealed outer doors. Provide main power

connection(s), control power connections,

compressor and fan motor start contactors,

current overloads, and factory wiring.

2. Power supply shall enter unit at a single

location, be 3 phase of scheduled voltage,

and connect to individual terminal blocks per

compressor. Separate disconnecting means

and/or external branch circuit protection (by

Contractor) required per applicable local or

national codes.

B. Exposed compressor, control and fan motor power

wiring shall be routed through liquid tight conduit.

2.07 ACCESSORIES AND OPTIONS

Some accessories and options supercede standard

product features. Your YORK representative will be

pleased to provide assistance.

A. Microprocessor controlled, Factory installed

Across-the-Line type compressor motor starters

as standard.

B. Outdoor Ambient Temperature Control

1. Low Ambient Control: Permits unit operation to

0°F ambient. Standard unit controls to 25°F

ambient. Low Ambient Control standard on

YCUL0096-0130 models.

2. High Ambient Control: Permits unit operation

above 115°F ambient.

C. Power Supply Connections:
1. Single Point Power Supply: Single point Termi-

nal Block for field connection and interconnect-

ing wiring to the compressors. Separate exter-

nal protection must be supplied, by others, in

the incoming power wiring, which must comply

with the National Electric Code and/or local

codes. Single Point Supply option available

on YCUL0046-0090 models and standard on

YCUL0016 - 0040 models.

2. Single Point or Multiple Point Power Supply

with individual System Breakers: Single or

Multiple Point Terminal Block(s) for field con

nection and factory interconnecting wiring to

factory supplied system breakers . Available

on YCUL0096-0130 models.

3. Single Point or Multiple Point Disconnect:

Single or Dual point Non-Fused Disconnect(s)

and lockable external handle (in compliance

with Article 440-14 of N.E.C.) can be supplied

to isolate the unit power voltage for servicing.

Separate external fusing must be supplied, by

others, in the in coming power wiring, which

must comply with the National Electric Code

and/or local codes.

4. Single Point Disconnect with Individual System

Breakers: Single point Terminal Block with Non-

Fused Disconnect and lockable external handle

(in compliance with Article 440-14 of N.E.C.)

can be supplied to isolate power voltage for

servicing. Factory interconnecting wiring from

disconnect to factory supplied circuit breakers.

Available on YCUL0096-0130 models.

5. Single Point Circuit Breaker: Single point Ter-

minal Block with Circuit Breaker and lockable

external handle (in compliance with Article 440

14 of N.E.C.) can be supplied to isolate power

voltage for servicing. Incoming power wiring

must comply with the National Electric Code

and/or local codes. Single Point Circuit Break

ers available on YCUL0016-0090 models.

D. Pressure & Temperature Transducers and Sen-

sors
1. Discharge Pressure Transducers: Permits unit

to sense and display discharge pressure.

2. Suction Pressure Transducers: Permits unit

to sense and display suction pressure. This

capability is standard on YCUL0076-0090

models. (This option is required for suction

pressure control on models YCUL0016-0066.)

3. Suction Temperature Sensors: Permits units to