Options and Accessories

POWER OPTIONS:

COMPRESSOR POWER CONNECTIONS – Single-point

(YCUL0016-0040) or multiple-point (YCUL0046-0130) ter-

minal block connection(s) are provided as standard. The

following power connections are available as options. (See

electrical data for specific voltage and options availability.)

(Factory-mounted.)

SINGLE-POINT SUPPLY TERMINAL BLOCK – (Available

on YCUL0046 - 0090 models (standard on YCUL0016 -

0040 models)). Includes enclosure, terminal-block and

interconnecting wiring to the compressors. Separate

external protection must be supplied, by others, in the

incoming compressor-power wiring. (Do not include this

option if either the Single-Point Non-Fused Disconnect

Switch or Single-Point Circuit Breaker options have been

included.)

SINGLE-POINT OR MULTIPLE-POINT SUPPLY TER-

MINAL BLOCK(S) WITH INDIVIDUAL SYSTEM BREAK-

ERS - (Available on YCUL0096-0130 models) Includes

single- or dual-point terminal block connection(s) with

factory interconnecting wiring from the terminal block to

factory supplied system circuit breakers.

SINGLE-POINT NON-FUSED DISCONNECT SWITCH (Avail-

able on YCUL0016-0090 models)

OR MULTIPLE-POINT

NON-FUSED DISCONNECT SWITCHES (Available on

YCUL0096-0130 models) – Unit-mounted disconnect

switch(es) with external, lockable handle (in compliance

with Article 440-14 of N.E.C.), can be supplied to isolate

the unit power voltage for servicing. Separate external fus-

ing must be supplied, by others in the power wiring, which

must comply with the National Electrical Code and/or local

codes.

SINGLE-POINT NON-FUSED DISCONNECT SWITCH

WITH INDIVIDUAL SYSTEM BREAKERS - (Available on

YCUL0096-0130 models) Includes unit-mounted disconnect

switch with external, lockable handles (in compliance with

Article 440-14 of N.E.C.) to isolate unit power voltage for

servicing. Factory interconnecting wiring is provided from

the disconnect switch to factory supplied system circuit

breakers.

SINGLE-POINT CIRCUIT BREAKER – (Available on

YCUL0016-0090 models) – A unit mounted circuit breaker

with external, lockable handle (in compliance with N.E.C.

Article 440-14), can be supplied to isolate the power volt-

age for servicing. (This option includes the Single-Point

Power connection.)

CONTROL TRANSFORMER – Converts unit power voltage to

115-1-60 (0.5 or 1.0 kVA capacity). Factory mounting includes

primary- and secondary-wiring between the transformer and

the control panel. (Factory-mounted.)

POWER FACTOR CORRECTION CAPACITORS – Will cor-

rect unit compressor power factors to a 0.90-0.95. (Factory

mounted).

CONTROL OPTIONS:

AMBIENT KIT (LOW) – (Available on YCUL0016-0090 models

only [standard on YCUL0096-0130models]) Units will operate

to 25°F (-4°C). This accessory includes all necessary compo-

nents to permit condensing unit operation to 0°F (-18°C). (This

option includes the Discharge Pressure Transducer / Readout

Capability option.) For proper head pressure control in appli-

cations below 25°F (-4°C) where wind gusts may exceed 5

mph, it is recommended that Optional Condenser Louvered

Enclosure Panels also be included. (Factory-mounted.)

AMBIENT KIT (HIGH) – Required if units are to operate when

the ambient temperature is above 115°F (46°C). Includes sun

shield panels and discharge pressure transducers. (This option

includes the Discharge Pressure Transducer / Readout Capa-

bility option). (Field-mounted).

BUILDING AUTOMATION SYSTEM INTERFACE – The fac-

tory addition of a Printed Circuit Board to accept a 4-20 mil-

liamp, 0-10VDC or contact closure input to reset the discharge

air temperature from a Building Automation System. (Only

one of following options can be offered on a unit at a time:

BAS, Remote Control Panel or Multi-unit Sequence Control).

(Factory mounted).
- (The standard unit capabilities include remote start-stop,

remote discharge air temperature reset via a PWM input

signal or up to two steps of demand (load) limiting depend-

ing on model.)

- (The standard control panel can be directly connected to

a YORK Building Automated System via the standard on

board RS485 communication port.)

LANGUAGE LCD AND KEYPAD DISPLAY – Spanish,

French, German, and Italian unit LCD controls and keypad

display available. Standard language is English.

DISCHARGE PRESSURE TRANSDUCERS AND READOUT

CAPABILITY(Available on YCUL0016 - 0090 models only

[standard on YCUL0096 - 0130]) The addition of pressure

transducers allows models to sense and display discharge

pressure. (This option as included with either the low or high

ambient kits). (Factory mounted).

SUCTION PRESSURE TRANSDUCERS AND READOUT

CAPABILITY (Available on YCUL0016-0066 models [stan-

dard on YCUL0076-0130 models]). The addition of suction

transducers allows models to sense and display suction

pressure. This option is required for suction pressure control

capability on YCUL0016-0066 models. (Factory mounted).

SUCTION TEMPERATURE READOUT – The addition of tem-

perature sensors allow models to sense and display suction