NOTES:
1. For lower or higher suction temperature applications, contact your nearest YORK Office for application requirements.
2. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system (For YCUL0016

- 0090 models only).

3. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.

ENGLISH UNITS

Design Parameters

YCUL

SUCTION

TEMPERATURE (°F)

AIR ON

CONDENSER (°F)

MIN

1

MAX

1

MIN

2

MAX

3

0016

35

55

0

125

0026

35

55

0

125

0030

35

55

0

125

0036

35

55

0

125

0040

35

55

0

125

0046

35

55

0

125

0050

35

55

0

125

0056

35

55

0

125

0060

35

55

0

125

0066

35

55

0

125

0076

35

55

0

125

0080

35

55

0

125

0086

35

55

0

125

0090

35

55

0

125

0096

35

55

0

125

0100

35

55

0

125

0106

35

55

0

125

0120

35

55

0

125

0130

35

55

0

125