Guide Specifications

PART 1 – GENERAL

1.01 SCOPE

A. The requirements of the General Conditions,

Supplementary Conditions, Division 1, and Draw-

ings apply to all Work herein.

B. Provide Microprocessor controlled, multiple-scroll

compressor, air-cooled, condensing units of the

scheduled capacities as shown and indicated on

the Drawings, including but not limited to:

1. Condensing Unit package

2. Electrical power and control connections

3. DX Central Station Air Handling connections

1.02 QUALITY ASSURANCE

A. Products shall be Designed, Tested, and installed in

compliance with applicable sections of the following

Standards and Codes:

1. ANSI/ASHRAE Standard 15 – Safety Code

for Mechanical Refrigeration

2. ASHRAE 90.1 - Energy efficiency compli-

ance.

3. ANSI/NFPA Standard 70 – National Electrical

Code (N.E.C.).

4. Conform to Intertek Testing Services, formerly

ETL, for construction of condensing units and

provide E.T.L./c E.T.L. Listing label.

5. Manufactured in facility registered to ISO

9002.

B. Factory Test: Condensing Unit shall be pressure-

tested, evacuated and given a nitrogen holding

charge and an initial oil charge, and shall be fac-

tory operational run tested to assure each control

device operates properly.

C. Warranty: Manufacturer shall Warrant all equipment

and material of its manufacture against defects in

workmanship and material for a period of one year

from date of initial start-up or eighteen (18) months

from date of shipment, whichever occurs first.

1.03 DELIVERY AND HANDLING

A. Unit shall be delivered to job site fully assembled,

and given nitrogen holding charge and a full oil

charge by the Manufacturer. (R-22 or HFC-407C

supplied by others).

B. Unit shall be stored and handled per Manufacturer’s

instructions.

PART 2 - PRODUCTS

2.01 CONDENSING UNITS MATERIALS AND

COMPONENTS

A. General: Install and commission, as shown on the

schedules and plans, factory assembled, charged,

and tested air cooled scroll compressor condensing

unit as specified herein. Condensing Unit shall be

designed, selected, and constructed using a refrig-

erant with Flammability rating of “1”, as defined by

ANSI/ASHRAE STANDARD - 34 Number Desig-

nation and Safety Classification of Refrigerants.

Condensing Unit shall include, but is not limited to:

a system with a single refrigerant circuit 35 tons

(123kW) and below, and not less than two refriger-

ant circuits above 35 tons (123kW), scroll compres-

sors, air-cooled condenser, refrigerant, lubrication

system, interconnecting wiring, safety and operating

controls including capacity controller, control center,

motor starting components, and special features as

specified herein or required for safe, automatic

operation.

B. Cabinet: External structural members shall be con-

structed of heavy gauge, galvanized steel coated with

baked on powder paint which, when subject to ASTM

B117, 500 hour, 5% salt spray test, yields minimum

ASTM 1654 rating of “6”

2.02 COMPRESSORS

Compressors: Shall be hermetic, scroll-type, includ-

ing:

1 Compliant design for axial and radial sealing.

2. Refrigerant flow through the compressor with

100% suction cooled motor.

3. Large suction side free volume and oil sump to

provide liquid handling capability.

4. Compressor crankcase heaters to provide extra

liquid migration protection.

5. Annular discharge check valve and reverse vent

assembly to provide low pressure drop, silent

shutdown and reverse rotation protection.

6. Initial Oil charge.

7. Oil Level sightglass.

8. Vibration isolator mounts for compressors.

9. Brazed-type connections for fully hermetic

refrigerant circuits.