Application data – York YCUL0016 User Manual

Page 116

Advertising
background image

YORK INTERNATIONAL

116

YORK INTERNATIONAL

117

FORM 150.63-EG1

UNIT LOCATION

The YCUL Condensing Units are designed for outdoor

installation. When selecting a site for installation, be

guided by the following conditions:

1.For outdoor locations of the unit, select a place having

an adequate supply of fresh air for the condenser.

2. Avoid locations beneath windows or between struc-

tures where normal operating sounds may be objec-

tionable.

3. Installation sites may be either on a roof, or at ground

level. (See FOUNDATION.)

4. The condenser fans are the propeller-type, and are

not recommended for use with duct work in the con-

denser air stream.

5. When it is desirable to surround the unit(s), it is rec-

ommended that the screening be able to pass the

required chiller CFM without exceeding 0.1" of water

external static pressure.

6. Protection against corrosive environments is available

by supplying the units with either copper fin, cured

phenolic, or epoxy coating on the condenser coils.

The phenolic or epoxy coils should be offered with

any units being installed at the seashore or where

salt spray may hit the unit.

In installations where winter operation is intended and

snow accumulations are expected, additional height

must be provided to ensure normal condenser air

flow.

Recommended clearances for units are given in DIMEN-

SIONS. When the available space is less, the unit(s)

must be equipped with the discharge pressure trans-

ducer option to permit high pressure unloading in the

event that air recirculation were to occur.

FOUNDATION

The unit should be mounted on a flat and level founda-

tion, ground or roof, capable of supporting the entire

operating weight of the equipment. Operating weights

are given in the PHYSICAL DATA tables.

ROOF LOCATIONS – Choose a spot with adequate

structural strength to safely support the entire weight

of the unit and service personnel. Care must be taken

not to damage the roof during installation. If the roof is

“bonded”, consult the building contractor or architect

for special installation requirements. Roof installations

should incorporate the use of spring-type isolators to

minimize the transmission of vibration into the building

structure.

Application Data

GROUND LEVEL INSTALLATIONS – It is important

that the units be installed on a substantial base that will

not settle, causing strain on the refrigerant lines and

resulting in possible leaks. A one-piece concrete slab

with footers extending below the frost line is highly rec-

ommended. Additionally, the slab should not be tied to

the main building foundation as noises will telegraph.

Mounting holes (11/16" diameter) are provided in the

steel channel for bolting the unit to its foundation. See

DIMENSIONS.

For ground level installations, precautions should be

taken to protect the unit from tampering by or injury to

unauthorized persons. Screws on access panels will pre-

vent casual tampering; however, further safety precau-

tions, such as unit enclosure options, a fenced-in enclo-

sure, or locking devices on the panels may be advisable.

Check local authorities for safety regulations.

REFRIGERANT PIPING

When sizing refrigerant pipe for split system air condi-

tioning, consideration must be given to the: (1) Suction

line pressure drop due to friction, (2) Liquid line pres-

sure drop due to friction, (3) Suction line velocity for oil

return, and (4) Liquid line pressure drop due to vertical

rise. Refer to DESIGN PARAMETERS for friction losses

for both the suction and liquid lines for the condensing

unit.

On a system where the evaporator blower is located

below the condensing unit, the suction line must be

sized for both pressure drop and oil return.

When the condensing unit is located below the evapora-

tor blower, the liquid line must be designed for pressure

drop due to friction loss and vertical rise. If the pressure

drop due to vertical rise and friction loss exceeds 30 psi,

some refrigerant will flash before it reaches the thermal

expansion valve.

All horizontal suction lines should be pitched at least 1/4

inch per foot in the direction of the refrigerant flow to aid

the return of oil to the compressor. All suction lines with

a vertical rise exceeding 3 feet should have a ‘P’ trap

at the bottom and the top to facilitate oil return. Suction

lines with a vertical rise exceeding 25 feet should be

trapped every 15 feet to provide drain points for the

oil when the circuit is deactivated. When the circuit is

reactivated, oil will return to the compressor more quickly

and in smaller slugs.

For more details, refer to ASHRAE Refrigeration Hand-

book, System Practices for Halocarbon Refrigerants.

Advertising
This manual is related to the following products: