Electrical data – York YCUL0016 User Manual

Page 108

Advertising
background image

YORK INTERNATIONAL

108

YORK INTERNATIONAL

109

FORM 150.63-EG1

Electrical Data

MODEL

YCUL

VOLT

HZ

SYSTEM #1 FIELD SUPPLIED WIRING

MCA

1

MIN N/F

DISC SW

2

D.E. FUSE

CKT. BKR.

5

INCOMING (LUGS) WIRE RANGE

6

MIN

3

MAX

4

MIN

MAX

TERMINAL BLOCK

(std)

NF DISC. SWITCHES

(opt)

CIR BREAKERS

(opt)

0096

200

60

251

400

300

350

300

350

# 6 - 400

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

230

60

233

250

300

300

300

300

# 6 - 400

(1) # 6 - 350

(1 or 2) 3/0 - 500

380

60

135

150

150

175

150

175

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

460

60

111

150

125

150

125

150

# 14 - 2/0

(1) # 6 - 350

(1) # 3 - 3/0

575

60

89

100

100

110

100

110

# 14 - 2/0

(1) # 6 - 350

(1) # 10 - 1/0

0100

200

60

251

400

300

350

300

350

# 6 - 400

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

230

60

233

250

300

300

300

300

# 6 - 400

(1) # 6 - 350

(1 or 2) 3/0 - 500

380

60

135

150

150

175

150

175

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

460

60

111

150

125

150

125

150

# 14 - 2/0

(1) # 6 - 350

(1) # 3 - 3/0

575

60

89

100

100

110

100

110

# 14 - 2/0

(1) # 6 - 350

(1) # 10 - 1/0

0106

200

60

274

400

300

300

300

300

(2) # 4 - 500

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

230

60

254

400

300

300

300

300

(2) # 4 - 500

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

380

60

148

200

175

175

175

175

# 14 - 2/0

(1) # 6 - 350

(1) # 3 - 3/0

460

60

122

150

150

150

150

150

# 14 - 2/0

(1) # 6 - 350

(1) # 10 - 1/0

575

60

98

150

110

110

110

110

# 14 - 2/0

(1) # 10 - 1/0

(1) # 10 - 1/0

0120

200

60

274

400

300

300

300

300

(2) # 4 - 500

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

230

60

254

400

300

300

300

300

(2) # 4 - 500

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

380

60

148

200

175

175

175

175

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

460

60

122

150

150

150

150

150

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

575

60

98

150

110

110

110

110

# 14 - 2/0

(1) # 6 - 350

(1) # 3 - 3/0

0130

200

60

359

400

400

450

400

450

(2) # 4 - 500

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

230

60

333

400

400

400

400

400

(2) # 4 - 500

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

380

60

194

250

225

225

225

225

# 6 - 400

(1) # 6 - 350

(1) # 6 - 350

460

60

159

200

175

200

175

200

# 6 - 400

(1) # 6 - 350

(1) # 6 - 350

575

60

128

150

150

150

150

150

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

MODEL

YCUL

VOLT

HZ

SYSTEM #2 FIELD SUPPLIED WIRING

MCA

1

MIN N/F

DISC SW

2

D.E. FUSE

CKT. BKR.

5

INCOMING (LUGS) WIRE RANGE

6

MIN

3

MAX

4

MIN

MAX

TERMINAL BLOCK

(std)

NF DISC. SWITCHES

(opt)

CIR BREAKERS

(opt)

0096

200

60

191

200

225

250

225

250

# 6 - 400

(1) # 6 - 350

(1) # 6 - 350

230

60

178

200

200

225

200

225

# 6 - 400

(1) # 6 - 350

(1) # 6 - 350

380

60

104

150

125

125

125

125

# 14 - 2/0

(1) # 6 - 350

(1) # 3 - 3/0

460

60

85

100

100

110

100

110

# 14 - 2/0

(1) # 10 - 1/0

(1) # 10 - 1/0

575

60

68

100

80

90

80

90

# 14 - 2/0

(1) # 10 - 1/0

(1) # 10 - 1/0

0100

200

60

251

400

300

350

300

350

# 6 - 400

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

230

60

233

250

300

300

300

300

# 6 - 400

(1) # 6 - 350

(1 or 2) 3/0 - 500

380

60

135

150

150

175

150

175

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

460

60

111

150

125

150

125

150

# 14 - 2/0

(1) # 6 - 350

(1) # 3 - 3/0

575

60

89

100

100

110

100

110

# 14 - 2/0

(1) # 6 - 350

(1) # 10 - 1/0

0106

200

60

259

400

300

350

300

350

# 6 - 400

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

230

60

241

250

300

300

300

300

# 6 - 400

(1) # 6 - 350

(1 or 2) 3/0 - 500

380

60

140

150

175

175

175

175

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

460

60

115

150

150

150

150

150

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

575

60

92

100

110

125

110

125

# 14 - 2/0

(1) # 6 - 350

(1) # 3 - 3/0

0120

200

60

274

400

300

300

300

300

(2) # 4 - 500

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

230

60

254

400

300

300

300

300

(2) # 4 - 500

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

380

60

148

200

175

175

175

175

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

460

60

122

150

150

150

150

150

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

575

60

98

150

110

110

110

110

# 14 - 2/0

(1) # 6 - 350

(1) # 3 - 3/0

0130

200

60

374

400

300

300

300

300

(2) # 4 - 500

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

230

60

354

400

300

300

300

300

(2) # 4 - 500

(1 or 2) 3/0 - 500

(1 or 2) 3/0 - 500

380

60

148

200

175

175

175

175

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

460

60

122

150

150

150

150

150

# 14 - 2/0

(1) # 6 - 350

(1) # 6 - 350

575

60

98

150

110

110

110

110

# 14 - 2/0

(1) # 6 - 350

(1) # 3 - 3/0

YCUL0096 - YCUL0130

MULTIPLE POINT POWER SUPPLY CONNECTIONS (see Fig. 3)

(Two Field Provided Power Supply Circuits to the condensing unit. Field connections to Factory Provided Terminal Blocks (standard), Non-Fused Disconnect

Switches (optional) or Individual System Circuit Breakers (optional) per electrical system.)

See Notes on page 100

Advertising
This manual is related to the following products: