Selection data – York YCUL0016 User Manual

Page 12

Advertising
background image

YORK INTERNATIONAL

12

YORK INTERNATIONAL

13

FORM 150.63-EG1

TABLE 5 – REFRIGERANT LINE PRESSURE DROPS (ENGLISH)

MODEL

NUMBER

YCUL

SYSTEM

NUMBER

1

NOMINAL

TONS

SUCTION LINE

LIQUID LINE

COPPER

TYPE L

INCHES O.D.

2

PRESSURE

DROP

PSI/100 FT.

VELOCITY

@NOMINAL

CAPACITY

IN FPM

4

NOMINAL

TONS

UNLOADED

COPPER

TYPE L

INCHES

O.D.

3

PRESSURE

DROP

PSI/100 FT.

0016

1

15

1-5/8

2.5

2400

7.5

3/4

4.5

5

2-1/8

0.6

1350

7/8

2.1

0026

1

20

1-5/8

4.3

3200

10

3/4

7.7

5

2-1/8

1.1

1800

7/8

3.5

0030

1

27

1-5/8

7.4

4320

13

7/8

6.1

2-1/8

1.9

2430

1-1/8

1.7

0036

1

31

2-1/8

2.4

2790

15

7/8

7.9

5

2-5/8

0.7

1860

1-1/8

2.2

0040

1

39

5

2-1/8

3.7

3510

13

1-1/8

3.4

5

2-5/8

1.3

2340

1-3/8

1.3

0046

1

21

1-5/8

4.7

3360

10

3/4

8.4

5

2-1/8

1.2

1890

7/8

3.8

2

21

1-5/8

4.7

3360

10

3/4

8.4

5

2-1/8

1.2

1890

7/8

3.8

0050

1

27

1-5/8

7.4

4320

13

7/8

6.1

2-1/8

1.9

2430

1-1/8

1.7

2

21

1-5/8

4.7

3360

10

3/4

8.4

5

2-1/8

1.2

1890

7/8

3.8

0056

1

27

1-5/8

7.4

4320

13

7/8

6.1

2-1/8

1.9

2430

1-1/8

1.7

2

27

1-5/8

7.4

4320

13

7/8

6.1

2-1/8

1.9

2430

1-1/8

1.7

0060

1

30

2-1/8

2.3

2700

15

7/8

7.4

5

2-1/8

0.8

1800

1-1/8

3.8

2

27

1-5/8

7.4

4320

13

7/8

6.1

2-1/8

1.9

2430

1-1/8

1.7

0066

1

31

2-1/8

2.4

2790

15

7/8

7.9

5

2-5/8

0.9

1860

1-1/8

2.2

2

31

2-1/8

2.4

2790

15

7/8

7.9

5

2-5/8

0.9

1860

1-1/8

2.2

Selection Data