Guide specifications – York YCUL0016 User Manual

Page 120

Advertising
background image

YORK INTERNATIONAL

120

YORK INTERNATIONAL

121

FORM 150.63-EG1

sense and display suction temperature.

E. Control Power Transformer: Converts unit power

voltage to 120-1-60 (500 VA capacity). Factory

mounting includes primary- and secondary-wiring

between the transformer and the control panel.

F. Motor Current Module: Capable of monitoring com-

pressor motor current. Provides extra protection

against compressor reverse rotation, phase-loss

and phase imbalance. Options consists of one

module per electrical system. (Factory mounted)

G. Power Factor Correction Capacitors: Provided to

correct unit compressor factors to a 0.90-0.95.

H. Condenser Coil Environmental Protection:

1. Pre-Coated: Epoxy coated aluminum fin stock

to guard from corrosive agents and insulate

against galvanic potential. For mild seashore

or industrial locations.

2. Copper Fin: Provide copper fins in lieu of

aluminum.

3. Post-Coated Dipped: Dipped-cured coating on

condenser coils for seashore and other corro-

sive applications (with the exception of strong

alkalis, oxidizers, and wet bromine, chlorine

and fluorine in concentrations greater than

100ppm).

I. Protective Condensing Unit Panels (Factory or Field

Mounted):
1. Louvered Panels (condenser coils only):

Painted steel as per remainder of unit cabinet,

over external condenser coil faces.

2. Wire Panels (full unit): Heavy gauge, welded

wire-mesh, coated to resist corrosion, to protect

condenser coils from incidental damage and

restrict unauthorized access to internal com-

ponents.

3. Louvered Panels (full unit): Painted steel as per

remainder of unit cabinet, to protect condenser

coils from incidental damage,visually screen

internal components, and prevent unauthorized

access to internal components.

4. Louvered/Wire Panels: Louvered steel panels

on external condenser coil faces, painted as

per remainder of unit cabinet. Heavy gauge,

welded wire-mesh, coated to resist corrosion,

around base of machine to restrict unauthorized

access.

J. Service Isolation valves: Service suction and dis-

charge (ball type) isolation valves are added to unit

per system. This option also includes a system high

pressure relief valve in compliance with ASHRAE

15. (Factory-mounted.)

K. Hot Gas By-Pass: Permits continuous, stable opera-

tion at capacities below the minimum step of unload-

ing to as low as 5% capacity (depending on both

the unit & operating conditions) by introducing an

artificial load. Hot gas by-pass is available installed

on one or both refrigerant circuit(s).

L. Microprocessor Membrane Keypad Graphics on in

lieu of Standard English:

1. French language.

2. German language.

3. Spanish language.

4. Italian language.

M. Chicago Code Relief Valves to meet Chicago Code

requirements.

N. Building Automation System (EMS) Reset Interface:

Condensing Unit to accept 4 to 20mA, 0 to 10 VDC,

or discrete contact closure input to reset the dis-

charge air temperature.

O. Remote Control Panel (Field Mounted): Auxiliary

panel for remote user interface for functions nor-

mally made at the unit control center. Available on

YCUL0016-0090 models.

P. OptiView Remote Control Panel (Field-mounted)

Graphical interface panel to remotely control and

monitor up to 8 units

Q. Sound Reduction (Factory Mounted):

1. Low speed, reduced noise fans

2. Compressor Acoustic Sound Blankets

R. Vibration Isolation (Field Mounted):

1. Neoprene Pad Isolators.

2. 1 Inch Deflection Spring Isolators: Level adjust-

able, spring and cage type isolators for mount-

ing under the unit base rails.

3. 2 Inch Deflection Seismic Isolators: Level

adjustable, restrained mounts in rugged welded

steel housing with vertical and

horizontal limit stops. Housings shall be

designed to withstand a minimum 1.0g accel-

Guide Specifications