Devicenet network scanner dvpdnet-sl – 2nd Ave. DVPDNET-SL DeviceNet Network Scanner DVP-0204520-02 User Manual

Page 11

Advertising
background image

DeviceNet Network Scanner DVPDNET-SL

DVP-PLC Operation Manual

9

Mapped D registers

DVPDNET-SL

index

Output mapping

Input mapping

4

D7750 ~ D7997

D7500 ~ D7747

5

D8250 ~ D8497

D8000 ~ D8247

6

D8750 ~ D8997

D8500 ~ D8747

7

D9250 ~ D9497

D9000 ~ D9247

8

D9750 ~ D9997

D9500 ~ D9747

4.2 I/O

Mapping

Table

Output mapping are

Input mapping area

D register

Mapping area

Data length

D register

Mapping area

Data length

D6250 ~ D6281

Explicit message
program request

32 words

D6000 ~ D6031

Explicit message
program response

32 words

D6282 ~ D6285 Bit-strobe command

4 words

D6032 ~ D6035

Status of nodes in the
scan list

4 words

D6286 Reserved

1word

D6036

DVPDNET-SL status

1 word

D6287 ~ D6476 DeviceNet output data

190 words

D6037 ~ D6226

DeviceNet input data

190 words

D6477 ~ D6497 Reserved

21 words

D6227 ~ D6247

Reserved

21 words

5

Constructing DeviceNet Network

In this section, we will present an application example, illustrating how to construct a DeviceNet network and

the configuration of the network. Before constructing a network, you have to first know clearly what the network

is for and start a preliminary planning for the data to be exchanged. The plan shall include the maximum

communication distance, slaves to be used, total length of data to be exchanged and so on. These information

will decide whether the network you construct is a reasonable one, or if it satisfies your needs, and even affect

the later-on network sustainability and flexibility of network capacity upgrade.

5.1

How to Construct a DeviceNet Network

Target

Using a remote digital I/O module to control RUN/STOP of VFD-B AC motor drive.

1. The connection

Advertising