DeviceNet Network Scanner DVPDNET-SL

DVP-PLC Operation Manual

26

editing area to 0.

„ When M1 = On, DVPDNET-SL will send out request message. Write 0004Hex into Class 99 >>

Instance 1 >> Attribue 2 of the target equipment (node address: 02). If the communication of

explicit message is successful, the slave will return with a response message.

„ When M1 = On, DVPDNET-SL will only send out request message once. If you would like it to

send out request message again, you will have to change ReqID.

„ When the writing is successfully done, the message responded from the target equipment will be

stored in D6000 ~ D6003.

7 Bit-Strobe

Command

7.1 Principle

of

Bit-Strobe

Bit-strobe is one of the standard I/O transmission methors for DeviceNet. The length of command is fixed to

8 bytes (i.e. 64 bits), and every bit corresponds to a slave.

Corresponding nodes on the network

PLC

device

b15

b14

b13

b1

b0

D6282

Node 15

Node 14

Node 13

Node 1

Node 0

D6283

Node 31

Node 30

Node 29

Node 17

Node 16

D6284

Node 47

Node 46

Node 45

Node 33

Node 32

D6285

Node 63

Node 62

Node 61

Node 49

Node 48

When b0 of D6282 = 0, the node 0 equipment will be selected, and it will need to respond with a message to

the master. When b0 and b1 of D6282 = 0, the node 0 and node 1 equipment will be selected, and they will beed

to respond with a message to the master.

b0

b1

b17

b15 b14

b30

b2

b18

b16

b31

D6283

Node 0

Node 1

Node 2

Node 14

D6282

In the bit-strobe mode, the master will not send control data to the slave node. However, when its

corresponding bit is set to 0, the slave node will have to respond with I/O data to the master. When its

corresponding bit is set to 1, the slave node will not have to respond with I/O data to the master.

8

Display of Node Status on Network

8.1

Display of Node Status in Scan List

DVPDNET-SL does read-time monitoring to the nodes in the scan list and maps the status of every node to a

bit. You can acquire the node status by monitoring D6032 ~ D6035. See the table below for the corresponding

relation between PLC devices and the nodes on the network: