DeviceNet Network Scanner DVPDNET-SL

DVP-PLC Operation Manual

26

editing area to 0.

„ When M1 = On, DVPDNET-SL will send out request message. Write 0004Hex into Class 99 >>

Instance 1 >> Attribue 2 of the target equipment (node address: 02). If the communication of

explicit message is successful, the slave will return with a response message.

„ When M1 = On, DVPDNET-SL will only send out request message once. If you would like it to

send out request message again, you will have to change ReqID.

„ When the writing is successfully done, the message responded from the target equipment will be

stored in D6000 ~ D6003.

7 Bit-Strobe

Command

7.1 Principle

of

Bit-Strobe

Bit-strobe is one of the standard I/O transmission methors for DeviceNet. The length of command is fixed to

8 bytes (i.e. 64 bits), and every bit corresponds to a slave.

Corresponding nodes on the network

PLC

device

b15

b14

b13

…

b1

b0

D6282

Node 15

Node 14

Node 13

…

Node 1

Node 0

D6283

Node 31

Node 30

Node 29

…

Node 17

Node 16

D6284

Node 47

Node 46

Node 45

…

Node 33

Node 32

D6285

Node 63

Node 62

Node 61

…

Node 49

Node 48

When b0 of D6282 = 0, the node 0 equipment will be selected, and it will need to respond with a message to

the master. When b0 and b1 of D6282 = 0, the node 0 and node 1 equipment will be selected, and they will beed

to respond with a message to the master.

b0

b1

b17

b15 b14

b30

b2

b18

b16

b31

D6283

Node 0

Node 1

Node 2

Node 14

D6282

In the bit-strobe mode, the master will not send control data to the slave node. However, when its

corresponding bit is set to 0, the slave node will have to respond with I/O data to the master. When its

corresponding bit is set to 1, the slave node will not have to respond with I/O data to the master.

8

Display of Node Status on Network

8.1

Display of Node Status in Scan List

DVPDNET-SL does read-time monitoring to the nodes in the scan list and maps the status of every node to a

bit. You can acquire the node status by monitoring D6032 ~ D6035. See the table below for the corresponding

relation between PLC devices and the nodes on the network: