DeviceNet Network Scanner DVPDNET-SL

DVP-PLC Operation Manual

23

„ Compulsory settings in IFD9502

Parameter

Set value

Explanation

Node address

02

Set the node address of IFD9502 to “02".

Baud rate

500kbps

Set the communication speed of IFD9502 and bus to
“500kbps”.

„ Compulsory settings in VFD-B

Parameter

Set value

Explanation

02-00

04

The main frequency is operated on RS-485 interface.

02-01 03

The operation commands are operated on the communication
interface. Operation by keys is valid.

09-00

01

Communication address of VFD-B: 01

09-01

03

Baud rate: 38,400

09-04

03

Modbus RTU mode. Data format <8, N, 2>

„ Explanations on devices

Explanation

PLC device

Content

15 14 13 12 11 10 9

8 7 6 5 4

3

2

1

0

D6250

0101Hex

ReqID = 01Hex

Command = 01Hex

D6251

0005Hex

Port = 00Hex

Size = 05Hex

D6252 0E02Hex

Service Code = 0EHex

MAC ID = 02Hex

D6253

0001Hex

High bye of Class ID =00Hex Low byte of Class ID = 01Hex

D6254

0001Hex

High byte of Instance ID =

00Hex

Low byte of Instance ID =

01Hex

Request

message

editing area

D6255

0001Hex

N/A

Attribute ID = 01Hex

D6000

0101Hex

ReqID = 01Hex

Status = 01Hex

D6001

0002Hex

Port = 00Hex

Size = 02Hex

D6002 8E02Hex

Service Code = 8EHex

MAC ID = 02Hex

Response

message

editing area

D6003 031FHex

High byte of Service Data =

03Hex

Low byte of Service Data =

1FHex

(3) PLC

program

MOV

H0101

D6250

M1002

ZRST

D6250

D6281

M0

MOV

H0005

D6251

MOV

H0E02

D6252

MOV

H0100

D6253

MOV

H0100

D6254

MOV

H0100

D6255

ZRST

D6000

D6031

Reset response message editing area
& request message editing area

ReqID = 01, Command = 01

Port = 00, Size = 05

Service Code = 0E, MAC ID = 02

Class ID to be read = 01

Instance ID to be read = 01

Attribute ID to be read = 01