Devicenet network scanner dvpdnet-sl – 2nd Ave. DVPDNET-SL DeviceNet Network Scanner DVP-0204520-02 User Manual

Page 21

Advertising
background image

DeviceNet Network Scanner DVPDNET-SL

DVP-PLC Operation Manual

19

Target

When X0 = On, VFD-B will start to run, and Y0 indicator will be On.
When X1 = On, VFD-B will stop, and Y0 indicator will be Off.

1. PLC

program:

MOV

H2

D6288

M1000

MOV

D6038

K4M20

M8

MOV

H1

D6288

MOV

H0100

D6287

MOV

H0000

D6287

MOV

D6037

K4M0

M9

M8

M9

M20

M21

END

Send the content in D6037 to K4M0.

Send the content in D6038 to K4M20.

When X0 = On, start VFD-B.

When X1 = On, stop VFD-B.

When VFD-B runs, Y0 = On.

When VFD-B stops, Y0 = Off.

2. Program

explanations:

„ The head instruction in the program, MOV, corresponds the content in D6037 to M0 ~ M15 and the

content in D6038 to M20 ~ M35.

„ See the table below for the corresponding relation between DeviceNet slave and PLC devices.

PLC device

15 14 13 12

11

10

9

8

7

6

5

4

3

2

1

0

D6037 X7 X6 X5 X4 X3 X2 X1 X0

N/A

D6038

Status of VFD-B

Status of LED on VFD-B

D6039

Frequency of VFD-B

D6040

Input

data

PLC device

15 14 13 12

11

10

9

8

7

6

5

4

3

2

1

0

D6287 Y7 Y6 Y5 Y4 Y3 Y2 Y1 Y0

N/A

D6288

Control word in VFD-B

D6289

Frequency in VFD-B

D6290

Output

data

„ When X0 = On, b8 of D6037 = 1. b8 of D6037 corresponds to M8, and therefore M8 = On. That is,

when X1 = On, M9 will be On.

„ D6288 corresponds to the control word in VFD-B. When M8 = On, execute [MOV H2 D6288] to run

VFD-B. When M9 = On, execute [MOV H1 D6288] to stop VFD-B.

„ b0 of D6038 corresponds to M20, b1 to M21, and so on. When VFD-B is in RUN status, b0 of D6038 =

1 and M20 will be On to execute [MOV H0100 D6287], which leads to Y0 = On. That is, when

VFD-B is in STOP status, M21 will be On to execute [MOV H0000 D6287], which leads to Y0 = Off.