Devicenet network scanner dvpdnet-sl – 2nd Ave. DVPDNET-SL DeviceNet Network Scanner DVP-0204520-02 User Manual

Page 20

Advertising
background image

DeviceNet Network Scanner DVPDNET-SL

DVP-PLC Operation Manual

18

Slave → DVPDNET-SL

Register in

DVPDNET-SL

Devices in slave

D6037H

Digital I/O module

X0 ~ X7 on DVP-16SP

D6037L N/A

D6038H

Status of LED on VFD-B

D6038L

Status of VFD-B

D6039H

High byte of frequency in VFD-B

D6039L

AC motor drive

Low byte of frequency in VFD-B

„

If the I/O data include control word and status word of RTU-DNET, the I/O data mapping of

DVPDNET-SL and its slave devices will be:

DVPDNET-SL → slave

Register in

DVPDNET-SL

Devices in slave

D6287H

High byte of control word in RTU-DNET

D6287L

RTU-DNET

control word

Low byte of control word in RTU-DNET

D6288H

Digital I/O module

Y0 ~ Y7 on DVP-16SP

D6288L N/A

D6289H

High byte of command in VFD-B

D6289L

Low bye of command in VFD-B

D6290H

High byte of frequency in VFD-B

D6290L

AC motor drive

Low byte of frequency in VFD-B

Slave → DVPDNET-SL

Register in

DVPDNET-SL

Devices in slave

D6037H

High byte of status word in RTU-DNET

D6037L

RTU-DNET

status word

Low byte of status word in RTU-DNET

D6038H

Digital I/O module

X0 ~ X7 on DVP-16SP

D6038L N/A

D6039H

Status of LED on VFD-B

D6039L

Status of VFD-B

D6040H

High byte of frequency in VFD-B

D6040L

AC motor drive

Low byte of frequency in VFD-B

3. Saving the configuration data

Select “File” => “Save” to save the current network configuration.

5.3 DeviceNet

Network

Control

In this section, we will introduce how to compile WPL program and control DeviceNet. The example given

below is particularly for I/O data excluding RTU-DNET control word and status word. You will have to slightly

modify the example program if the I/O data include RTU-DENT control word and status word.