LED status

Indication

How to correct

Red light

blinking

Error in communication

Check the digital indicator and eliminate the error.

Red light on

Network error; cannot check
duplicate ID; bus-off (chek
the digital indicator)

1. Make sure all the devices have their unique node

address.

2. Check the network for correcting media installation

and baud rate.

3. Check if the node address of DVPDNET-SL is valid.

4. Check if the network power is normal.

9.3 MS

LED

LED status

Indication

How to correct

Off

No power

Make sure DVPDNET-SL is powered.

Green light

blinking

The master is not configured.

Configure the scan list and re-download it to

DVPDNET-SL.

Green light on

Normal operation

--

Red light

blinking

Some slaves encounter
communication error.

Check the digital indicator and make sure the salve
information in the scan list is consistent with the salve
actually connected.

Red light on

Internal error

1. Check if the configuration is valid.

2. Re-power it. If the error still exists, send it back to the

factory for repair.

9.4

MS & NS LED

LED status

NS LED

MS LED

Indication

How to correct

Off

Off

No power

Make sure DVPDNET-SL is powered.

Off

Green light

on

Duplicate ID check has not
completed.

Make sure at least 1 node or more are
communicating in the network, and the baud
rate is the same as the setting in DVPDNET-SL.

Red light on

Green light

on

MAC ID detection failure or
bus-off

Change the MAC ID setting and re-power
DVPDNET-SL.

Red light on

Red light

blinking

No 24 VDC power from
DeviceNet network

1. Check if the network cable is correctly

connected to DVPDNET-SL.

2. Check the 24 VDC network power.

Red light on Red light on Hardware error

Go to your manufacturer or distributor for
problem-solving.

9.5

Digital Indicator LED

Code

Indication

How to correct

0 ~ 63

Node address of
DVPDNET-SL (in normal
operation)

--

80

DVPDNET-SL is in STOP
status.

Turn the PLC MPU to RUN and start I/O data
exchange.

F0

Duplicate MAC ID check
failure

Check the node address and re-power DVPDNET-SL.

F1

No slave device in the scan
list.

Configure the scan list and download it to
DVPDNET-SL.