22

VEGACOM 557 Siemens

S5 functional component

5 S5 functional component

For the STEP 5 user program, internal functional components (HTB handling components)
HTB SYNCHRON, HTB FETCH and HTB RECEIVE are required. To call up the internal function
components, these must be loaded first from the automation device AG S5. The menu selec-
tion is then as follows: Object > Components > Transfer > AG file.

5.1 Synchron order

After the starting-up phase, the CP expects a SYNCHRON order. This is necessary for the
handling of the FETCH / SEND orders. The SYNCHRON component is generally called up with
the STEP 5 user program in the organisation components OB20, OB21 and OB22.

Calling up of handling components SYNCHRON

SPA

FB

249

with Simatic S5-115U CPU 942 B

Para-

Format

Meaning

meter

SSNR

KY

Interface number
KY = 0,y

y = 0 … 255

The logical number of the interface on which the concerned order can be
found.
See switch position on CP (J53).

BLGR

KY

Block size
KY = 0,y

y=1,2,3,4, 5 for block size 16,32,64, 128 and 256 Bytes.

PAFE

BY

Error indication with parameter setting failure
BY = MB 0, … MB 255; AB 0, …, AB 127
Information of a byte, in which a parameter setting failure is entered

Example:

Call up in OB20. Also valid for OB21 and OB22

OB 20

C:CP524_ST.S5D LAE=11

Network 1 0000 Output

:SPA FB 249

Name :SYNCHRON

SSNR : KY 0,0

BLGR : KY 0,4

Block size 128

PAFE : MB 50

Parameter failure in tag byte 50

:BE