VEGACOM 557 Siemens

S5 functional component

Call up of the Fetch and Receive component for the indicating values

The program reads in the indicating values for the VEGAMET instruments (DISBUS) or
VEGALOG instruments (LOGBUS). The Fetch order was determined in the programming
package COM 525 with order number 1. The statements on the data destination had been
carried out in the programming package with the order determination. Therefore the destina-
tion parameters ZTYP, DBNR, ZANF and ZLAE are negligible when calling up the RECEIVE
component.

FB 1 C:CP524_ST.S5D LAE = 62

Network 1 0000 Output

Name :TEST

:O M 1.1

:ON M 1.1

VKE = 1 force, so that FETCH

:

is worked on in any case

:

:SPA FB 246

enquire FETCH-component

Name :FETCH

SSNR : KY 0,0

Interface no. = 0

A-NR : KY 0,1

Order number = 1

ANZW : MW 10

Indication double word up from MW10

ZTYP : KC DB Data destination (of indication values) in data component

DBNR : KY 0,3

... number 3

ZANF : KF +0

Data destination to DW0

ZLAE : KF +42*

fetch 6 indication values (of 2 signal conditioning instruments

VEGAMET 1 and 2)

PAFE : MB 2

Parametr. failure in MB 2

:

:

:

:

:

:

:

:O M 1.1

:ON M 1.1

VKE = 1 force, so that FETCH

:

is worked on in any case

:

:SPA FB 245

enquire RECEIVE-component

Name :RECEIVE

SSNR : KY 0,0

Interface no. = 0

A-NR : KY 0,0

Order number = 1

ANZW : MW 12

Indication double word up from MW12

ZTYP : KC DB

Data destination in data component

DBNR : KY 0,0

ZANF : KF +0

ZLAE : KF +0

PAFE : MB 3

:

:

:

:

:

:

:BE

*

6DW as offset (see page 23), 6DW for VEGAMET 1, 6DW for VEGAMET 2