VEGA VEGACOM 557 Siemens 3964 and 3964 R procedure with RK 512 User Manual

Page 28

Advertising
background image

28

VEGACOM 557 Siemens

Saving of the relay information from VEGALOG out of data component

1 data word will be reserved per LOGBUS card. In total, 32 data words will be covered by
VEGALOG.

DW

Card address

0

1

1

2

2

3

3

4

4

5

31

32

Contents of the data words: Bits

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Status reser- reser- reser- reser- reser- Relay Relay Relay Relay Relay Relay Relay Relay Relay Rel.

ved

ved

ved

ved

ved

10

9

8

7

6

5

4

3

2

1

Status = 0 –> Relay information is valid
Status = 1 –> Relay information is invalid.

Parameter setting of the FETCH component

ZLAE is an important parameter, indicating the length of the data block. The value is depend-
ent on the number of indicating values:

VEGAMET (DISBUS):

ZLAE value = 14 + VEGAMET module no. • 14

VEGALOG (LOGBUS):

ZLAE value = number of indicating values • 2

SSNR:

The interface number corresponds to the switch position in the CP (standard feature
= 0)

A-NR:

The order number corresponds to the setting in the programming package COM
525

ANW:

Statement of a double marker word for status description

ZTYP:

KC DB

Data destination is data component

DBNR:

KY 0

Data component number

ZANF:

KF +0

Initial word in DB is data word 0. With != 0 the data sector is shifted by

this value.

ZLAE :

KF +value data length in bytes value = see above

PAFE :

Statement of a marker byte for indication of parameter setting failures

S5 functional component