VEGA VEGACOM 557 Siemens 3964 and 3964 R procedure with RK 512 User Manual

Page 29

Advertising
background image

VEGACOM 557 Siemens

29

S5 functional component

Parameter setting of the RECEIVE component

The information on the data destination, parameter : ZTYP, DBNR, ZANF and ZLAE are irrel-
evant as this information was already defined in the programming package COM 525 with the
order determination.

SSNR:

The interface number corresponds to the switch positions in the CP.
(standard feature = 0)

A-NR:

The order number corresponds to the setting in the programming package COM
525

ANW:

Statement of a double marker word for status description

ZTYP:

KC DB

Data destination is data component

DBNR:

KY 0,0

Data component number, here irrelevant

ZANF:

KF +0

Initial word in DB, here irrelevant

ZLAE:

KF +0

Data length in bytes, here irrelevant

PAFE:

Statement of a marker byte for indication of parameter setting failures

Application example for VEGAMET

Call up in OB20, OB21 and OB22

OB 20

C:CP524_ST.S5D LAE=11

Network 1 0000 Output

:SPA FB 249

Name :SYNCHRON

SSNR : KY 0,0

BLGR : KY 0,3

Block size 64

PAFE : MB 50

Parameter error in merker byte 50

:BE