VEGA VEGACOM 557 Siemens 3964 and 3964 R procedure with RK 512 User Manual

Page 31

Advertising
background image

VEGACOM 557 Siemens

31

S5 functional component

Call up of the Fetch and Receive component for the relay information

...

FB 2 C:CP524_ST.S5D LAE = 62

Network 1 0000 Output

Name :REL

:O M 1.1

:ON M 1.1

VKE = 1 force, so that FETCH

:

is worked on in any case

:

:SPA FB 246

enquire FETCH-component

Name :FETCH

SSNR : KY 0,0

Interface no. = 0

A-NR : KY 0,2

Order number = 2 for relay information

ANZW : MW 11

Indication double word up from MW11

ZTYP : KC DB

Data destination(the indication values) in data component

DBNR : KY 0,4

... Number 3

ZANF : KF +0

Data destination to DW0

ZLAE : KF +32

32 words (all relays)

PAFE : MB 4

Parametr.failure in MB 4

:

:

:

:

:

:

:

:O M 1.1

:ON M 1.1

VKE = 1 force, so that FETCH

:

is worked on in any case

:

:SPA FB 245

enquire RECEIVE-component

Name :RECEIVE

SSNR : KY 0,0

Interface no. = 0

A-NR : KY 0,0

Order number = 1

ANZW : MW 12

Indication double word up from MW12

ZTYP : KC DB

Data destination in data component

DBNR : KY 0,0

ZANF : KF +0

ZLAE : KF +0

PAFE : MB 3

:

:

:

:

:

:

:BE

Note:
In the total program only one RECEIVE necessary.