35

Supplement

Table: Comparison of important interface data

Interfaces

RS 232 C

RS 422 A

RS 485

Transmission

asym.

symmetr.

symmetr.

Number of drivers

1

1

32

Number of receivers

1

10

32

Transmission distance

15 m

1200 m

1200 m

max. transmission rate

20 KBit/s

10 MBit/s

10 MBit/s

Emitter
Permissible driver
output voltage

±25 V

–0.25…6 V

–7…12 V

Driver output signal
-

without load

±15 V

± 5 V

± 5 V

-

with load

± 5 V

± 2 V

±1.5 V

Driver load

3…7 kOhm

100 Ohm

54 Ohm

Receiver
Input voltage

±15 V

±7 V

–7…12 V

Sensitivity

±3 V

±200 mV

±200 mV

Input resistance

3…7 kOhm

4 kOhm

12 kOhm

10km

1,2km

1km

100m

30m

15m

100

1k

10k 20k

100k

1M

Bit/s 10M

RS 422-A
RS 485

RS 232-C

Distance

Transmission rate

Diagram: Distance –– Transmission rate