VEGA VEGACOM 557 Siemens 3964 and 3964 R procedure with RK 512 User Manual

Page 23

Advertising
background image

VEGACOM 557 Siemens

23

S5 functional component

5.2 Handling components for reading in of data (indicating values)

For reading in the indicating values from the VEGAMET instruments and saving them in a PLC
data component, the handling component HTB FETCH is necessary to place orders and the
HTB RECEIVE to fetch and save data.

Handling component FETCH

The FETCH component gives the order to the CP to fetch data of a communication partner. The
receipt of the data however is carried out by the component RECEIVE.

Calling up of handling component FETCH

SPA

FB

246

with Simatic S5-115U CPU 942 B

Para-

Format

Meaning

meter

SSNR

KY

Interface number
KY = 0,y

y = 0 … 255

The logical number of the interface on which the concerned order can be
found.
See switch position on CP (J53).

A-NR

KY

Order number
KY = 0,y

y = 0 … 255

y = order number

ANZW

W

Anzeigewort
W= DBx , MWx

x = 0 … 255

Addresse of the double word (4 bytes !!)

In the double word, the processing status of a certain order is shown

ZTYP

KC

Type of the data destination

DBNR

KY

Data component number
KY = 0,y

y = 0 … 255

Number of the data component in which the data should be saved

ZANF

KF

Initial data block address of the destination

ZLAE

KF,KH

Data block length of the destination

PAFE

Error indication with parameter setting failure
BY = MB 0, … MB 255; AB 0, …, AB 127
Information of a byte, in which a parameter setting failure is entered