6. Moisture Control Options

38

PNEG-1743 Vision for Tower Dryers

This scheme also has a feature called “Auto-Centering”. If the controller is staying in HI the majority of the
time, it probably means the metering roll setpoint (MED) is set too low. To alleviate this problem, the unload
rate is continually averaged. Once an hour, the controller changes the metering roll setpoint (MED) to the
averaged value. In the example above, if the controller stayed in HI for an entire hour, it would change the
metering roll setpoint to 62% and would now act according to the table below.

NOTE: A “Max Grain Temp” safety is available for this scheme. By enabling this feature, the dryer will

shutdown and issue a warning if the grain temperature exceeds the “Max Grain Temp” value.

Setup procedure

1. Press the “Stop” button on the control panel if the dryer is running.

2. From the “Setup” screen, select “Drying Mode”, then “Continuous Flow”.

3. From the “Drying Mode Selection” screen, select “M/C Setup” to access “Continuous Flow Setup”.

4. Select “Temperature” from the “Continuous Flow Control Schemes” group.

5. If desired, enable the “Max Grain Temp” safety.

6. Select “5 Speed” from the “Temp Based Options” group.

7. If Auto-Centering is desired, select “Auto-Centering” from the “5 Speed Setup” group until the

“Enabled” box is checked.

8. Select “5 Speed Setup” from the “5 Speed Setup” group.

9. Press the “Select” button until “Positive Inner Limit” is circled in red.

10. Use the “Inc” and “Dec” buttons on the left to adjust the “Temperature” offset for the “Inner” set.

11. Use the “Inc” and “Dec” buttons on the right to adjust the “Metering Speed” offset of the “Inner” set.

12. Press the “Select” button until the “Positive Outer Limit” is circled in red.

13. Use the “Inc” and “Dec” buttons on the left to adjust the “Temperature” offset for the “Outer” set.

14. Use the “Inc” and “Dec” buttons on the right to adjust the “Metering Speed” offset of the “Outer” set.

15. Return to the “Default Operation Screen”.

16. Press the “Meter Roll Speed” adjustment knob to access the “Modifying Meter Roll Speed

Setpoints” screen.

17. Adjust the meter roll speed to the desired setpoint and press “Accept/Exit”.

18. Return to the “Default Operation Screen”.

19. Press the “M/C” button and enter a grain temperature setpoint.

20. Turn the “Unload” switch to the “AUTO” position.

21. Press the “Start” button on the control panel.

LO (Outer)

M-LO (Inner)

MED

M-HI (Inner)

HI (Outer)

Grain

Temperature

Less than or

equal to 97°

Between 98°

and 99°

At 100°

Between 101°

and 102°

Greater than or

equal to 103°

Unload Rate

50%

59%

62%

65%

74%