Grain Systems PNEG-1743 User Manual

Page 47

Advertising
background image

8. Safety Circuit Shutdown Messages

PNEG-1743 Vision for Tower Dryers

47

0E08 - Main I/O - Out of Grain Timer (OOG) Expired

This message indicates that the dryer has run low on grain and the out of grain timer has timed out,
shutting the dryer down. The unload auger will continue to run so it can clean out the remaining grain
before shutting down.

0E09 - Main I/O - Network Connection Failed

This error is generated whenever the master display board (lower control panel) has lost its communications
link with the Input/Output board (upper control panel door) and the fan/heater boards. Check the Ethernet
cable jacks to make sure they are plugged in tightly.

0E13 - Main I/O - Metering Roll Drive Failure

This message indicates that the meter rolls are not turning, possibly due to the meter roll speed adjustment
being set too low. It also could indicate that there is a defective meter roll sensor, the metering roll drive
system has failed to turn, or there is a broken chain or a component has jammed the metering roll. This
message can occur if the input is not receiving a 5 volt pulse on terminal J4-04 on the Input/Output board.

0E15 - Main I/O - Valve Proving System Failure

In CE regulations, a Dung’s valve proving system is required. It is attached to the low side of the regulator.
If there is a leak present, the contacts will open causing the shutdown of the dryer.

0E16 - Main I/O - J2-04 - User Safety 2 Open

If a user would like to add a safety device to the Vision system, a normally closed contactor/relay can be
attached to this input and the dryer will shutdown if it opens. This is normally jumped out if not in use.

0E17 - Main I/O - J2-05 - User Safety 3 Open

If a user would like to add a safety device to the Vision system, a normally closed contactor/relay can be
attached to this input and the dryer will shutdown if it opens. This is normally jumped out if not in use.

0E18 - Main I/O - J2-02 - Metering Motor Overload

If an overload device is monitoring the meter system, this input is used to shutdown the dryer if there is a
problem. Possibly a plugged meter system would trip this safety.

0E19 - Main I/O - J2-06 - User Safety 4 Open

If a user would like to add a safety device to the Vision system, a normally closed contactor/relay can be
attached to this input and the dryer will shutdown if it opens. This is normally jumped out if not in use.

Advertising