Technical Data

MOTOR INSULATION RESISTANCE READINGS
Normal Ohm/Megohm readings, ALL motors, between all leads and ground

Condition of Motor and Leads

OHM Value

Megohm Value

New motor, without power cable

20,000,000 (or more)

20.0

Used motor, which can be reinstalled in well

10,000,000 (or more)

10.0

Motor in well – Readings are power cable plus motor

New motor

2,000,000 (or more)

2.0

Motor in reasonably good condition

500,000 to 2,000,000

0.5 – 2.0

Motor which may be damaged or have

damaged power cable

20,000 to 500,000

0.02 – 0.5

Do not pull motor for these reasons

Motor definitely damaged or with

damaged power cable

10,000 to 20,000

0.01 – 0.02

Pull motor and repair

Failed motor or power cable

Pull motor and repair

Less than 10,000

0 – 0.01

To perform insulation resistance test, open breaker and

disconnect all leads from QD control box or pressure switch.

Connect one ohmmeter lead to any motor lead and one to metal drop pipe

or a good ground. R x 100K Scale

WARNING

Hazardous voltage

can shock, burn or

cause death.

Generator Operation

FAILURE TO USE A MANUAL OR AUTOMATIC

TRANSFER SWITCH WHEN GENERATOR IS USED AS

STANDBY OR BACKUP CAN CAUSE SHOCK, BURNS

OR DEATH. FOLLOW THE GENERATOR MANUFACTURER’S

INSTRUCTIONS CAREFULLY. TWO WIRE DATA IS ONLY FOR

PSC TYPE MOTORS, SPLIT PHASE 2 WIRE SHOULD BE 50%

LARGER THAN 3 WIRE GENERATOR RATING.

Generator Operation

Technical Data

CAUTION

Minimum Generator Rating

Externally Regulated

Internally Regulated

Motor HP kW kVA kW kVA

.5 2.5 3.1 1.8 2.2

.75 3.5 4.4 2.5 3.1

1 5 6.3 3.2 4

1.5 6 7.5 4 5

.5

2

2.5

1.5

1.9

.75 3 3.8 2 2.5

1 4 5 2.5

3.2

1.5 5 6.3 3 3.8

2

7.5

9.4

4

5

3

10

12.5

5

6.3

5

15

18.8

7.5

9.4

7.5

20

25

10

12.5

10 30 37.5 15 18.8

2 Wire

PSC Only

3 Wire

1Ø or 3Ш