WARNING

Hazardous voltage

can shock, burn or

cause death.

Troubleshooting

DISCONNECT AND LOCKOUT ELECTRICAL POWER BE-

FORE ATTEMPTING ANY SERVICE. FAILURE TO DO SO CAN

CAUSE SHOCK, BURNS OR DEATH.

Symptom

Probable Cause

Recommended Action

PUMP MOTOR

NOT RUNNING

LITTLE OR

NO LIqUID

DELIVERED

BY PUMP

1. Motor thermal protector tripped

a. Incorrect control box

b. Incorrect or faulty electrical

connections

c. Faulty thermal protector

d. Low voltage

e. Ambient temperature of control

box/starter too high

f. Pump bound by foreign matter

g. Inadequate submergence

2. Open circuit breaker or blown fuse

3. Power source inadequate for load
4. Power cable insulation damage
5. Faulty power cable splice

1. Allow motor to cool, thermal

protector will automatically reset

a – e. Have a qualified electrician

inspect and repair, as required

f. Pull pump, clean, adjust set

depth as required

g. Confirm adequate unit

submergence in pumpage

2. Have a qualified electrician inspect

and repair, as required

3. Check supply or generator capacity
4 – 5. Have a qualified electrician

inspect and repair, as required

1. Faulty or incorrectly installed

check valve

2. Pump air bound

3. Lift too high for pump

4. Pump bound by foreign matter

5. Pump not fully submerged

6. Well contains excessive amounts

of air or gases

7. Excessive pump wear
8. Incorrect motor rotation

– three phase only.

1. Inspect check valve, repair as

required

2. Successively start and stop pump

until flow is delivered

3. Review unit performance, check

with dealer

4. Pull pump, clean, adjust set depth

as required

5. Check well recovery, lower pump

if possible

6. If successive starts and stops does

not remedy, well contains excessive

air or gases

7. Pull pump and repair as required
8. Reverse any two motor electrical

leads