Advanced Settings include:
• Trigger conditions for No Water/Loss of Prime Fault
• Calibration of power threshold used for No Water/Loss of

Prime Fault

• No Water/Loss of Prime Restart Time Fixed or Progressive
• Size of pressure variation used for No Flow detection
Note: In the text below, “Dry Well” and “No Water/Loss of

Prime” mean the same thing.

HOW SETTINGS ARE CHANGED
Advanced settings are made by holding down pushbutton(s)

while at the same time switching a DIP switch in a specific

direction. In all cases, power to the controller must be on

and the pump stopped in order to make the desired change.

If needed, the pump can be forced to stop by disconnecting

one wire from the switch input terminal block.
After settings have been changed, the controller must run

and stop the pump for the setting to be stored in memory.

Once this is done, removing power will not affect settings.

There is no limit to how many times the settings can be

changed.
Settings are described below. Where applicable, after a

description, there is a table showing which pushbutton(s)

and DIP switch to use to make a particular setting. The

tables show which pushbutton(s) to hold down, which DIP

switch to flip and the direction to flip it. If the DIP switch is

in the wrong starting position, move it before pressing the

pushbutton.
For example, suppose a setting calls for flipping a DIP

switch from left to right but it is already in the right

position. In that case, before pressing any pushbuttons, you

would first flip the switch to the left position. Then you

would press the pushbutton and flip the switch to the right.
You can switch the DIP switches all you want without

affecting any of the advanced settings as long as no

pushbuttons are pressed. You can change settings as many

times as you want. Be sure to put DIP switches back in the

required positions after the setting are done.

RESETTING THE FACTORY DEFAULTS
Controller settings can always be returned to factory

defaults by pressing both pushbuttons for 10 or more

seconds while controller is powered and the pump is

stopped. Default controller settings are:
• Pressure Setting = 50 PSI
• No Water/Loss of Prime trigger = Low Pressure AND

Low Power

• No Water/Loss of Prime power level = factory default

which is based on motor overload switch

• No Water/Loss of Prime restart time = increasing

1/10/20/30/60 min.

• Pressure variation = +/-2 PSI.

NO WATER/LOSS OF PRIME TRIGGER CONDITIONS
No Water/Loss of Prime fault has four choices for trigger

conditions. The factory default is to trigger when power

and pressure are both low. This is the best choice for most

applications. The other three choices are Low Power only,

Low Pressure only and disabled. Low Pressure is defined as

being less than 75% of pressure setting.

No Water/

Pushbutton

DIP Switch

Direction to

Loss of Prime

to Hold

to Flip

Flip

Trigger Condition

Down

DIP Switch

Low Pressure +

Low Power*

Top

Left to Right

Low Pressure Only

Top

Right to Left

Low Power Only

Bottom

Left to Right

Disabled

Right to Left

* Factory Default

NO WATER/LOSS OF PRIME POWER CALIBRATION
While pump is pumping water press and hold both

pushbuttons until LED turns orange. This will calibrate

the power level at which the No Water/Loss of Prime

fault occurs. This calibration is especially important when

Low Power only is used as the trigger condition. Hold the

pushbuttons for at least 3 seconds to get the LED to turn

orange. The controller requires the pump to be running at

least at 75% of full speed before allowing calibration. If the

LED does not turn orange it may be necessary to flow more

water and/or temporarily increase the pressure setting to

get the pump speed to 75%. If power is not calibrated, the

controller will use a default value based on the setting of the

motor overload setting dial.