Mounting controller, Pump and piping, Check valve – Xylem IM183 R09 3AB2 & 5AB2 Aquavar ABII Variable Speed Pump Controller User Manual

Page 4: For a 5 psi pressure drop set-up, For a 20 psi pressure drop set-up, Wiring pressure transducer

Advertising
background image

4

Mounting Controller

Three screws are provided for mounting the enclosure.
Using the enclosure as a guide, select a mounting location.

First install the top screw in the mounting surface leaving

the head of the screw approximately

1

8

" from the surface.

Hang the enclosure on this screw. Finish by installing the

two bottom screws and tightening the top screw. Be sure

to leave a minimum of 6" of clearance on each side of the

controller to ensure proper cooling.

Pump and Piping

Do not install any valves (except check

valves), flow control devices or filters

between the pressure transducer and the pump. It is

allowable to run branches off the pipe between the pump

and transducer as long as no flow restricting devices are

between the pump and transducer.
NOTICE: The terms Transducer and Pressure Sensor are

equal and interchangeable.

EXPLODING TANK CAN INJURE OR

KILL.

Always protect the tank from over pressure by installing

a pressure relief valve large enough to limit the system

pressure below the maximum working pressure of the tank.

Install the tank at a point in the system where the maximum

possible system pressure cannot exceed the maximum

working pressure of the tank. Install the pressure relief valve

at the tank.

Avoid property damage caused by pressure

relief valve opening. Pipe the pressure relief

valve discharge to a drain or other location so that property

damage and flooding will not occur.

Locate the tank and transducer where they

will not freeze.

Ensure the system pressure setting does not exceed the

maximum working pressure of the tank.
For optimum performance, as a minimum, we recommend

using the same size pipe as the pump discharge between the

pump and the tank. Smaller diameter pipe may severely limit

the maximum capacity of the system. On long runs, larger

pipe may be beneficial for optimum performance and flow.

Check Valve

Use a spring check valve between pump and tank for

reliable turn-off when flow stops.

TANK SIZING AND TANK PRESSURE SETTING -

Refer to Table 1 for recommended tank size. On pre-existing

systems, larger tanks may be used.

Table 1: Systems with Small Tanks

Pump Size

Minimum Tank

GPM

Total Volume

5 - 6

2

7 - 8

2

10 -12

2

13 -15

4

18 - 20

4

25 - 28

5

33 - 35

7

40 - 45

9

55 - 60

12

75 - 80

15

For a 5 PSI Pressure Drop Set-up:

Set the tank pressure, while tank is empty of water, to 20 psi

below the desired system pressure setting. Ex. for a 50 psi

system pressure, charge the tank to 30 psi. *

For a 20 PSI Pressure Drop Set-up:

Set the tank pre-charge to 30 psi below the desired system

pressure setting. Ex. for a 50 psi system pressure, charge the

tank to 20 psi. *

* The tank pre-charge is always checked with the tank empty of water.

Wiring Pressure Transducer

Transducer wires must never be in same

conduit with power wires. There should

always be a minimum of 12" between transducer wires

and power wires. Failure to separate these wires can cause

controller malfunctions.
The pressure transducer cable is pre-wired at the factory. If

desired, the length of the cable can be changed. The cable

can also be put in conduit to protect against damage.
To change the length of the transducer cable:
• Cable length cannot exceed 200'.
• Disconnect transducer wires from terminal block by

pushing down on tabs at rear of block one at a time and

pulling the wires out of the terminal.

• Splice additional cable to transducer wire, cut off excess as

required.

• Reconnect wires to terminal block. Be sure wire colors

match labels on circuit board (B = Black, R = Red, W =

White).

To put the transducer cable in conduit, do the following:

Disconnect the cable from the terminal block and remove

the cable strain relief in the bottom of the enclosure.

Starting at the enclosure, run flexible or rigid ½" conduit to

where the transducer is located. The last few feet of conduit

adjacent to the transducer will need to be flexible. The

conduit must be well supported – NO stress can be placed

on the pressure transducer connector. Use a strain relief

bushing to seal around the pressure transducer connector.

After reconnecting the transducer wires to

the terminal block and ground terminal, tug

on each wire individually to ensure they are tight.

Any exposed metal in the system piping,

including transducer case, must be grounded

to the service entrance per NFPA 70: National Electrical

Code, Article 250.
The transducer cable has a Green ground wire and a ground

clamp supplied to facilitate grounding the transducer. See

Figure 1.

WARNING

WARNING

CAUTION

CAUTION

Figure 1: Transducer Grounding

CAUTION

CAUTION

CAUTION

Advertising