Motor Wires – See Table 2

NOTE: A MINIMUM OF 75ºC COPPER WIRE IS

MANDATORY.
Refer to the Table 2 for wire sizing and maximum wire

lengths. Charts are designed to limit voltage drop to 5%.
Figure 2 shows the terminal block where the motor and

input wires connect. The circuit board near the terminal

block is labeled to show where to connect the motor wires.

For all motors, the green wire from the motor must be

attached to the terminal labeled GND.
For 3Ø motors with red, black and yellow wires, connect

the red wire to RED, black wire to BLK and yellow wire to

YEL.
Note: If there is more than 50 feet of wire from the

controller to the motor, consult factory for selection of an

output load filter (load reactor).

Input Power

SHOCK OR ELECTROCUTION

HAZARD

Connect a ground wire from the service panel to the

terminal marked GND. Controller has high leakage to

ground. Controller ground terminal must be connected to

the service entrance ground terminal. Failure to do so will

result in high voltage being present on the controller chassis.

Connect two “hot” wires from the 2 pole circuit breaker to

the terminals marked L1 and L2.

The input power system used must be a grounded power

system. The voltage measured from L1 to L2 must be in the

range of 196Vac to 265Vac. The voltage measured from

L1 to GND must be equal to the voltage measured from

L2 to GND. These voltages must be within the range of

120Vac +/- 10%. Reduced input voltage will reduce system

performance.
Do not use a Ground Fault Circuit Interrupter (GFCI) with

this product or nuisance tripping will result.

Wire and Conduit

Factory installed input and output power leads may be
supplied with the controller. Use 75º C or higher rated
UL type copper wire. Use of Metal Conduit with Metal
Conduit liquid tight Connectors is recommended for all
electrical connections.

Figure 2: Wiring Connections

L1 L2 GND

GND RED BLK YEL

Incoming Power

Wires to Motor

DANGER

Table 2

Circuit Breaker, Wire and Generator Sizing

Circuit

1Ø Input Wiring

3Ø Output Wiring*

Generator

Model

Breaker

Size

Length (ft)

Size

Length (ft) Size

(KW)

3AB2 30

10 AWG

179

14 AWG

50

8100

8 AWG

261

5AB2 50

6 AWG

244

12 AWG

50

13300

4 AWG

390

* Consult factory for selection of an output load filter (load reactor) for output wire lengths greater than 50 feet.