Xylem IM183 R09 3AB2 & 5AB2 Aquavar ABII Variable Speed Pump Controller User Manual

Page 7

Advertising
background image

7

3: INSTALLER PRE-START SELECTIONS
DRIVE SETTINGS AND PROTECTION
Setting the Minimum Frequency Switch

The Minimum Frequency Switch (figure 3) is used to set

the minimum speed of the motor. This allows the controller

to fit a wide range of applications. Select a Minimum

Frequency of 10 Hz if the pressure at the pump’s suction

is within 20 PSI of the desired pressure setting. Select a

Minimum Frequency of 30 Hz if the pressure at the pump’s

suction is more than 20 PSI below the desired pressure

setting, such as when pumping from a tank or if drawing a

suction lift.

If used with a submersible well pump,

minimum frequency switch must be set to 30

Hz. Failure to do this will cause the motor thrust bearing to

wear prematurely.

Setting the Ramp Setting

The position of the Ramp Setting Switch (figure 3)

determines how fast the controller can change the speed

of the motor. A Slow Ramp Setting allows the controller

to work better in applications where the average demand

for water is low (less than 3 GPM or about 1 faucet). A

Fast Ramp Setting allows the controller to work better in

applications where demand for water is high because the

motor is allowed to change speed faster.

Note:

The Ramp Setting is preset at the factory for the “6

O‘Clock” position which is a half way point between fast

and slow. If “Hunting” or pressure fluctuation occurs, turn

dial to slower setting.

Setting Dry Run Restart Switch

The controller detects when pump has no water or has

lost prime. The Dry Run Restart Switch determines how

many times this error can occur in an hour. If set to CONT

(continuous), it will always restart. If set to 5X, it will

restart 5 times before it will disable pump and display “No

Water/Loss of Prime” error (2 red blinks). “No Water/Loss

of Prime” error can be cleared by removing power from

controller for 1 minute. Check water supply.

Low Pressure Cut-Off

This fault is disabled for the first 10 minutes of pump run

time after power up to allow the system to be purged.
ON Position - Used for constant pressure systems. The

drive will turn off if the system pressure drops 20 PSI

below the system set point pressure for 30 seconds.

This fault must be manually reset, it will not clear

automatically, this may prevent property damage if a pipe

breaks.
OFF Position - Use for open discharge situations such as

filling a pond or tank, or whenever the system pressure

will be 20 PSI or more below the system set point

pressure.

Pressure Drop – 5 PSI or 20 PSI

The pressure drop before the pump restarts can be set to

the standard 5 PSI or to 20 PSI.
The 20 PSI setting results in fewer starts for systems with

leaks. It is recommended for irrigation systems. It will

require a tank pre-charge adjustment. See Tank Sizing and

Tank Pressure Setting.

CURRENT LIMIT PROTECTION
Motor Overload Setting Dial

Failure to properly adjust the Motor

Overload Setting before applying power may

damage the motor or wire and void the warranty.

• Use Figures 3 and 4 to determine which controller and

setting to use. Note that some 200V motors require

upsizing to the next larger controller.

• Set the Motor Overload - Turn the dial pointer to align

with the motor’s service factor amps (SFA). Choose the

amperage value on UIB that is closest to the SFA listed on

the motor nameplate but not higher.

• If the output current exceeds the motor overload setting,

the controller will limit current by reducing the output

voltage and frequency. If the controller reduces the output

frequency to 40 Hz and the current still exceeds the

motor overload setting, the controller will shut down and

indicate Over Current error (4 red blinks).

Purge the System of Air

• Insure that plumbing connections are tight and wire

connections are correct.

• Partially open a valve and turn power to controller on.
• Run the pump and controller with the furthest and

highest faucets or valves in the system open. This will

allow all air to escape the piping system.

• When flow is constant, close the faucets or valves and

allow the system pressure to reach the 50 PSI pre-set

pressure and shutdown.

Controller Status Indicator

(Light Visible Through

Window in Cover)

The controller status indicator light has 3 possible modes:
• Solid green = Standby, pump not running. There is no

water flow or the SWITCH INPUT is open.

• Blinking green = Pump running. There is flow (possibly a

leak) and the SWITCH INPUT terminals are connected to

each other (closed).

• Red = Error/Fault. Light will blink to indicate a particular

fault. See Troubleshooting Section for Fault Codes.

PRESSURE ADJUSTMENT – Only if pressure

other than 50 PSI is desired:

• Adjust tank pressure according to the desired set pressure

- see Tank Sizing and Tank Pressure Setting section.

• Open a faucet and allow pump to start and purge the

system of air.

• When pressure gauge reaches 50, Press and Hold the

Increase pushbutton until the desired pressure shows on

the gauge.

• The larger the tank the longer it will take to increase

pressure.

• When desired pressure is reached, close the faucet and

allow the system to shut down.

Pump size determines the maximum flow and head which

can be provided, if flow or head are not sufficient and

rotation on three-phase units has been verified, a larger

pump is required.

3. INSTALLER PRE-START SELECTIONS

WARNING

CAUTION

Advertising