MANUAL RESET OF NO WATER/

LOSS OF PRIME FAULT
While setting up and testing the system it is convenient to

have a quick way to clear a No Water/Loss of Prime fault.

Pressing both pushbuttons while the controller has this fault

will clear it and resets the restart time to 1 min. Continuing

to hold the pushbuttons down for an additional 10s will

allow the pump to come up to speed and No Water/Loss of

Prime Power Calibration to occur. The pump is not allowed

to stop while any pushbuttons are held down.

NO WATER/LOSS OF PRIME RESTART TIME
After a No Water/Loss of Prime fault occurs, the controller

waits a period of time. This period of time can be chosen

to be fixed at 1 minute or increasing in length with each

occurrence of the fault. The factory default is for restart

time to increase each time this fault occurs. The controller

will “forget” one of these faults for every ½ hour of run

time. This allows the restart time to automatically shrink

once a No Water/Loss of Prime condition is resolved.

Manually resetting the fault by pressing both pushbuttons

will also clear the restart time back to 1 minute.

No Water/

Pushbutton

DIP Switch

Direction to

Loss of Prime

to Hold

to Flip

Flip

Restart Time

Down

DIP Switch

Increasing

1/10/20/30/60 min.*

Both Top

Left to Right

Fixed 1 min.

Right to Left

* Factory Default

SIZE OF PRESSURE VARIATION FOR FLOW

DETECTION
The controller uses pressure variation to detect when flow

has stopped. The factory default is for the pressure to vary

+/– 2 PSI. The other choices available are +/– 1 PSI and

+/– 3 PSI. Ideally one would like the smallest pressure

variation while maintaining quick turn off when flow stops.

Too small of a variation may result in the controller not

turning off and/or turning off when it shouldn't. If either

of these problems occur, increasing the pressure variation

should solve the problem. Ensuring the tank has the correct

pre-charge pressure setting and having a spring check valve

on the pump side of the tank and pressure transducer will

provide most reliable turn off performance and allow the

smallest pressure variation setting.

Pushbutton

DIP Switch

Direction to

Pressure Variation

to Hold

to Flip

Flip

Down

DIP Switch

1 PSI

Top

2nd

Right to Left

2 PSI*

from Top

Left to Right

3 PSI

Bottom

Left to Right